EG-325BE7-C23 C
4.20 kW
Defrost: None
Product code: EG-230BE7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,974 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 14.9 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-230BE7-C25 C | None |
|---|---|
| EG-230BE7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.63 | 1.64 | 1.66 | 1.68 | 1.68 | 1.68 | 1.66 | 1.71 | 1.83 | 1.99 | 1.95 | 1.94 | 1.92 | 1.91 |
| 5 | 2.10 | 2.14 | 2.19 | 2.23 | 2.24 | 2.24 | 2.23 | 2.27 | 2.41 | 2.62 | 2.55 | 2.52 | 2.48 | 2.43 |
| 6 | 2.55 | 2.64 | 2.71 | 2.78 | 2.82 | 2.83 | 2.82 | 2.86 | 3.03 | 3.29 | 3.19 | 3.15 | 3.09 | 2.99 |
| 7 | 2.98 | 3.11 | 3.22 | 3.33 | 3.40 | 3.43 | 3.42 | 3.47 | 3.68 | 3.98 | 3.86 | 3.81 | 3.73 | 3.61 |
| 8 | 3.35 | 3.53 | 3.69 | 3.83 | 3.93 | 3.98 | 3.99 | 4.05 | 4.30 | 4.67 | 4.55 | 4.49 | 4.40 | 4.25 |
| 9 | 3.73 | 3.95 | 4.13 | 4.32 | 4.44 | 4.51 | 4.54 | 4.61 | 4.89 | 5.31 | 5.17 | 5.11 | 5.02 | 4.86 |
| 10 | 4.06 | 4.33 | 4.59 | 4.81 | 4.96 | 5.05 | 5.09 | 5.17 | 5.49 | 5.95 | 5.80 | 5.74 | 5.63 | 5.45 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.802 |
| SC2 | 0 | 8 | 4.053 |
| SC3 | -18 | 7 | 3.365 |
| SC4 | -25 | 6 | 2.713 |
| SC5 | -34 | 6 | 2.575 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.