EG-430BC7-C21 C
7.58 kW
Defrost: None
Product code: EG-235BE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,289 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 21.7 m² |
| Inner volume | 6.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EG-235BE7-C21 C | None |
|---|---|
| EG-235BE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.86 | 2.86 | 2.87 | 2.88 | 2.87 | 2.85 | 2.82 | 2.89 | 3.08 | 3.33 | 3.26 | 3.23 | 3.18 | 3.12 |
| 5 | 3.75 | 3.81 | 3.87 | 3.92 | 3.94 | 3.92 | 3.88 | 3.95 | 4.20 | 4.54 | 4.41 | 4.37 | 4.31 | 4.23 |
| 6 | 4.61 | 4.75 | 4.88 | 4.99 | 5.05 | 5.06 | 5.02 | 5.08 | 5.39 | 5.84 | 5.65 | 5.59 | 5.49 | 5.33 |
| 7 | 5.36 | 5.57 | 5.77 | 5.95 | 6.07 | 6.14 | 6.15 | 6.24 | 6.63 | 7.20 | 6.98 | 6.89 | 6.76 | 6.55 |
| 8 | 6.10 | 6.38 | 6.62 | 6.87 | 7.04 | 7.13 | 7.17 | 7.26 | 7.71 | 8.37 | 8.17 | 8.08 | 7.94 | 7.71 |
| 9 | 6.75 | 7.13 | 7.48 | 7.80 | 8.01 | 8.12 | 8.18 | 8.30 | 8.81 | 9.56 | 9.33 | 9.23 | 9.07 | 8.79 |
| 10 | 7.35 | 7.84 | 8.29 | 8.68 | 8.96 | 9.13 | 9.21 | 9.34 | 9.92 | 10.76 | 10.50 | 10.38 | 10.20 | 9.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.499 |
| SC2 | 0 | 8 | 7.262 |
| SC3 | -18 | 7 | 6.007 |
| SC4 | -25 | 6 | 4.875 |
| SC5 | -34 | 6 | 4.644 |
| A | 2097 mm |
|---|---|
| B | 685 mm |
| C | 310 mm |
| F | 630 mm |
| E1 | 893 mm |
| E | 1785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 2097 mm |
|---|---|
| Width | 685 mm |
| Height | 310 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.