EG-430AB7-C25 C
5.18 kW
Defrost: None
Product code: EG-330BC7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,421 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 14.9 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 42 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-330BC7-C25 C | None |
|---|---|
| EG-330BC7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.93 | 1.96 | 1.98 | 2.01 | 2.01 | 2.01 | 1.99 | 2.04 | 2.17 | 2.36 | 2.31 | 2.29 | 2.26 | 2.22 |
| 5 | 2.51 | 2.58 | 2.64 | 2.70 | 2.74 | 2.75 | 2.73 | 2.78 | 2.96 | 3.21 | 3.12 | 3.10 | 3.06 | 3.00 |
| 6 | 3.04 | 3.17 | 3.28 | 3.39 | 3.47 | 3.51 | 3.51 | 3.57 | 3.79 | 4.11 | 4.00 | 3.96 | 3.90 | 3.80 |
| 7 | 3.50 | 3.68 | 3.85 | 4.01 | 4.11 | 4.18 | 4.22 | 4.29 | 4.56 | 4.96 | 4.86 | 4.81 | 4.74 | 4.63 |
| 8 | 3.97 | 4.20 | 4.42 | 4.62 | 4.75 | 4.85 | 4.90 | 4.98 | 5.30 | 5.77 | 5.65 | 5.59 | 5.50 | 5.36 |
| 9 | 4.37 | 4.67 | 4.96 | 5.22 | 5.40 | 5.52 | 5.59 | 5.69 | 6.05 | 6.58 | 6.43 | 6.37 | 6.27 | 6.10 |
| 10 | 4.73 | 5.11 | 5.47 | 5.78 | 6.02 | 6.18 | 6.25 | 6.38 | 6.78 | 7.38 | 7.24 | 7.16 | 7.05 | 6.85 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.236 |
| SC2 | 0 | 8 | 4.983 |
| SC3 | -18 | 7 | 4.055 |
| SC4 | -25 | 6 | 3.284 |
| SC5 | -34 | 6 | 3.072 |
| A | 1786 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E2 | 480 mm |
| E | 1475 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1786 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.