EG-330AE4-C25 C
7.07 kW
Defrost: None
Product code: EG-330BE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,709 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 35.2 m² |
| Inner volume | 5.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-330BE4-C25 C | None |
|---|---|
| EG-330BE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.82 | 2.87 | 2.93 | 2.99 | 3.01 | 3.02 | 3.00 | 3.09 | 3.29 | 3.59 | 3.51 | 3.49 | 3.46 | 3.43 |
| 5 | 3.56 | 3.68 | 3.79 | 3.89 | 3.95 | 3.96 | 3.95 | 4.02 | 4.28 | 4.65 | 4.52 | 4.47 | 4.40 | 4.29 |
| 6 | 4.25 | 4.44 | 4.62 | 4.77 | 4.88 | 4.93 | 4.92 | 5.00 | 5.30 | 5.76 | 5.59 | 5.52 | 5.42 | 5.25 |
| 7 | 4.86 | 5.13 | 5.37 | 5.59 | 5.73 | 5.81 | 5.83 | 5.92 | 6.29 | 6.83 | 6.65 | 6.57 | 6.45 | 6.24 |
| 8 | 5.47 | 5.81 | 6.13 | 6.41 | 6.58 | 6.69 | 6.73 | 6.83 | 7.25 | 7.86 | 7.65 | 7.56 | 7.41 | 7.16 |
| 9 | 6.00 | 6.43 | 6.83 | 7.19 | 7.43 | 7.58 | 7.63 | 7.74 | 8.21 | 8.90 | 8.67 | 8.56 | 8.39 | 8.09 |
| 10 | 6.48 | 7.01 | 7.51 | 7.95 | 8.25 | 8.44 | 8.53 | 8.63 | 9.16 | 9.92 | 9.68 | 9.56 | 9.37 | 9.02 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.682 |
| SC2 | 0 | 8 | 6.825 |
| SC3 | -18 | 7 | 5.654 |
| SC4 | -25 | 6 | 4.616 |
| SC5 | -34 | 6 | 4.296 |
| A | 1786 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E2 | 480 mm |
| E | 1475 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1786 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.