EG-425AE4-C23 C
6.31 kW
Defrost: None
Product code: EG-330BE7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,961 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 22.1 m² |
| Inner volume | 5.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-330BE7-C25 C | None |
|---|---|
| EG-330BE7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.47 | 2.49 | 2.52 | 2.54 | 2.55 | 2.54 | 2.52 | 2.59 | 2.77 | 3.01 | 2.95 | 2.93 | 2.90 | 2.88 |
| 5 | 3.18 | 3.25 | 3.32 | 3.38 | 3.41 | 3.41 | 3.38 | 3.45 | 3.67 | 3.98 | 3.86 | 3.82 | 3.76 | 3.68 |
| 6 | 3.86 | 3.99 | 4.12 | 4.23 | 4.29 | 4.31 | 4.29 | 4.35 | 4.61 | 5.00 | 4.85 | 4.79 | 4.69 | 4.55 |
| 7 | 4.47 | 4.67 | 4.85 | 5.02 | 5.13 | 5.19 | 5.20 | 5.27 | 5.59 | 6.07 | 5.88 | 5.80 | 5.68 | 5.50 |
| 8 | 5.03 | 5.30 | 5.55 | 5.77 | 5.92 | 6.00 | 6.03 | 6.11 | 6.49 | 7.04 | 6.86 | 6.78 | 6.66 | 6.45 |
| 9 | 5.59 | 5.93 | 6.24 | 6.52 | 6.69 | 6.81 | 6.85 | 6.95 | 7.38 | 8.00 | 7.80 | 7.71 | 7.57 | 7.33 |
| 10 | 6.07 | 6.50 | 6.89 | 7.23 | 7.48 | 7.62 | 7.68 | 7.80 | 8.28 | 8.97 | 8.75 | 8.65 | 8.49 | 8.21 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.754 |
| SC2 | 0 | 8 | 6.113 |
| SC3 | -18 | 7 | 5.071 |
| SC4 | -25 | 6 | 4.115 |
| SC5 | -34 | 6 | 3.889 |
| A | 1786 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E2 | 480 mm |
| E | 1475 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1786 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.