Skip to Content

Unit cooler EG-335CG4-C21 C

Unit cooler EG-335CG4-C21 C
Illustrative photo

Producer: Karyer · Line: EG (General)

Product code: EG-335CG4-C21 C

Cooling capacity i
13.31 kW
Air flow
4,774 m³/h
Fin spacing
4.2 mm
Air throw
15 m
Fans
3 × ⌀350 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EG — EG - angled ceiling-type unit cooler
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 35 — Ø350 mm
  • D
    Dimensional data - coil size letter: C — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 21 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 4,774 m³/h
Air throw 15 m
External surface 62.0 m²
Inner volume 10.7 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 58 kg
Fans
Quantity 3
Diameter 350 mm
Speed 1,340 rpm
Power 495 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 54.0 dB(A)
Sound power 75.7 dB(A)
Energy class D
Connections
Inlet Ø22
Outlet Ø28
Defrost
EG-335CG4-C21 C None
EG-335CG4-C21 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
12.844 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 5.31 5.48 5.64 5.78 5.85 5.85 5.80 6.03 6.45 7.03 6.88 6.83 6.78 6.72
5 6.63 6.93 7.21 7.45 7.59 7.63 7.58 7.76 8.26 8.98 8.71 8.61 8.45 8.20
6 7.81 8.25 8.66 9.01 9.23 9.34 9.33 9.52 10.11 11.00 10.66 10.50 10.27 9.88
7 8.87 9.54 10.02 10.50 10.82 10.98 10.98 11.17 11.86 12.86 12.47 12.29 12.01 not rated
8 9.94 10.69 11.39 12.00 12.41 12.62 12.64 12.84 13.62 14.75 14.31 14.09 not rated not rated
9 ≈ 10.83 11.77 12.64 13.41 13.95 14.23 14.32 14.49 15.35 16.62 16.14 15.88 not rated not rated
10 ≈ 11.63 12.76 13.83 14.77 15.33 15.74 15.90 16.16 17.14 18.54 18.01 17.71 not rated not rated

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 18.012
SC2 0 8 12.844
SC3 -18 7 10.646
SC4 -25 6 8.655
SC5 -34 6 7.910

Dimensions

Dimension drawing of EG-335CG4-C21 C
Dimension drawing
Dimensions as drawn
A 2447 mm
B 740 mm
C 370 mm
F 685 mm
E1 718 mm
E2 700 mm
E 2135 mm
D IN 1 x Ø22
D OUT 1 x Ø28
Overall [mm]
Length 2447 mm
Width 740 mm
Height 370 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.