EG-235CE4-C21 C
8.06 kW
Defrost: None
Product code: EG-430AC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,186 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 31.5 m² |
| Inner volume | 5.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø22 |
| EG-430AC4-C25 C | None |
|---|---|
| EG-430AC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.01 | 3.13 | 3.24 | 3.33 | 3.38 | 3.40 | 3.39 | 3.51 | 3.75 | 4.08 | 4.02 | 3.99 | 3.97 | 3.93 |
| 5 | 3.78 | 3.98 | 4.16 | 4.33 | 4.44 | 4.51 | 4.53 | 4.65 | 4.96 | 5.41 | 5.30 | 5.26 | 5.19 | 5.09 |
| 6 | 4.44 | 4.76 | 5.00 | 5.24 | 5.40 | 5.51 | 5.55 | 5.68 | 6.05 | 6.59 | 6.45 | 6.40 | 6.32 | 6.18 |
| 7 | 5.09 | 5.48 | 5.84 | 6.15 | 6.38 | 6.52 | 6.58 | 6.72 | 7.16 | 7.80 | 7.61 | 7.54 | 7.43 | 7.24 |
| 8 | ≈ 5.64 | 6.14 | 6.60 | 7.02 | 7.32 | 7.48 | 7.59 | 7.75 | 8.25 | 8.99 | 8.79 | 8.71 | 8.57 | 8.33 |
| 9 | ≈ 6.14 | 6.75 | 7.33 | 7.79 | 8.17 | 8.44 | 8.60 | 8.79 | 9.36 | 10.20 | 10.00 | 9.89 | 9.74 | 9.45 |
| 10 | ≈ 6.58 | 7.31 | 7.94 | 8.55 | 9.04 | 9.38 | 9.60 | 9.83 | 10.48 | 11.41 | 11.20 | 11.09 | 10.91 | 10.59 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.201 |
| SC2 | 0 | 8 | 7.751 |
| SC3 | -18 | 7 | 6.254 |
| SC4 | -25 | 6 | 5.000 |
| SC5 | -34 | 6 | 4.504 |
| A | 3546 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø22 |
| Length | 3546 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.