EG-430AC4-C21 C
8.62 kW
Defrost: None
Product code: EG-430BE7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,948 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 29.8 m² |
| Inner volume | 8.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 58 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EG-430BE7-C25 C | None |
|---|---|
| EG-430BE7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.36 | 3.37 | 3.40 | 3.44 | 3.44 | 3.43 | 3.40 | 3.50 | 3.74 | 4.06 | 3.98 | 3.96 | 3.93 | 3.89 |
| 5 | 4.34 | 4.41 | 4.49 | 4.56 | 4.59 | 4.59 | 4.55 | 4.64 | 4.93 | 5.35 | 5.20 | 5.15 | 5.07 | 4.96 |
| 6 | 5.27 | 5.42 | 5.57 | 5.70 | 5.77 | 5.79 | 5.75 | 5.83 | 6.19 | 6.71 | 6.50 | 6.42 | 6.30 | 6.10 |
| 7 | 6.15 | 6.38 | 6.60 | 6.81 | 6.94 | 7.00 | 6.99 | 7.07 | 7.50 | 8.12 | 7.87 | 7.77 | 7.61 | 7.36 |
| 8 | 6.93 | 7.25 | 7.55 | 7.83 | 8.01 | 8.11 | 8.13 | 8.25 | 8.75 | 9.49 | 9.25 | 9.14 | 8.96 | 8.65 |
| 9 | 7.71 | 8.13 | 8.51 | 8.83 | 9.06 | 9.20 | 9.25 | 9.38 | 9.95 | 10.79 | 10.51 | 10.39 | 10.20 | 9.87 |
| 10 | 8.40 | 8.92 | 9.41 | 9.83 | 10.13 | 10.31 | 10.37 | 10.52 | 11.16 | 12.09 | 11.79 | 11.65 | 11.44 | 11.06 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.792 |
| SC2 | 0 | 8 | 8.247 |
| SC3 | -18 | 7 | 6.871 |
| SC4 | -25 | 6 | 5.565 |
| SC5 | -34 | 6 | 5.308 |
| A | 2266 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E2 | 480 mm |
| E | 1955 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2266 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.