- Catalogue
- Unit coolers
- EL (Under Counter)
EL (Under Counter)
- Application
- Cubic, Commercial
- Air discharge
- Single
- Refrigerants
- R134a, R22, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R448A, R449A, R450a, R452a, R454A, R454C, R455A, R507A, R513a, R744
- Capacity
- 0.24–0.47 kW
- Fans
- ⌀120, ⌀170 mm
- Max. working pressure
- 25 bar
Model nomenclature
How to read the model codes of this series, with an example.
-
A
Model code (series) EL = EL - under-counter cooler
-
B
Number of fans — Number of fans (one digit).
-
C
Fan diameter 12 = Ø120 mm15 = Ø150 mm
-
D
Dimensional data - coil size letter — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows — Second letter of the dimensional data = number of tube rows (coil depth): A=2, B=3, C=4, D=5, E=6, G=8, I=10, K=12 (alphabet position + 1). E = 6 tube rows
-
F
Fin spacing — Nominal fin spacing in mm (1-2 digits). Karyer catalogue: 4=4.20, 5=5.50; fan 12=Ø120, 15=Ø150. The exact pitch is per model (e.g. 4 covers 3.8 to 4.6 mm). 4 = Fin spacing about 4 mm5 = Fin spacing about 5 mm
-
G
Generation code — Karyer design generation letter; Karyer publishes no further decoding. C = Generation C
-
H
Fan data 21 = Ø120: 230V/1Ph/50Hz, 4-pole22 = Ø150: 230V/1Ph/50Hz, 4-pole
-
J
Option suffix (variant) — Optional, on BRI variant codes only: " ED" = electric defrost variant; no suffix = standard variant. ED = Electric defrost
| Model | Cooling capacity [kW] i Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 % | Fin spacing [mm] | Fans | Air throw [m] | Air flow [m³/h] | Defrost | Variants |
|---|---|---|---|---|---|---|---|
| EL-112AE4-C21 C | 0.24 kW | 4.2 | 1 × ⌀120 | 1 | 90 | None, Electric |
Variants (2)
|
| EL-112BE4-C21 C | 0.29 kW | 4.2 | 1 × ⌀120 | 1 | 105 | None, Electric |
Variants (2)
|
| EL-212AE4-C21 C | 0.30 kW | 4.2 | 2 × ⌀120 | 1 | 123 | None, Electric |
Variants (2)
|
| EL-115AE5-C22 C | 0.35 kW | 5.5 | 1 × ⌀170 | 1 | 182 | None, Electric |
Variants (2)
|
| EL-212BE4-C21 C | 0.37 kW | 4.2 | 2 × ⌀120 | 1 | 143 | None, Electric |
Variants (2)
|
| EL-215AE5-C22 C | 0.39 kW | 5.5 | 2 × ⌀170 | 1 | 223 | None, Electric |
Variants (2)
|
| EL-115BE5-C22 C | 0.44 kW | 5.5 | 1 × ⌀170 | 1 | 217 | None, Electric |
Variants (2)
|
| EL-215BE5-C22 C | 0.47 kW | 5.5 | 2 × ⌀170 | 1 | 269 | None, Electric |
Variants (2)
|
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Downloads
- EL-112AE4-C21 C — product datasheet (PDF)
- EL-112BE4-C21 C — product datasheet (PDF)
- EL-212AE4-C21 C — product datasheet (PDF)
- EL-115AE5-C22 C — product datasheet (PDF)
- EL-212BE4-C21 C — product datasheet (PDF)
- EL-215AE5-C22 C — product datasheet (PDF)
- EL-115BE5-C22 C — product datasheet (PDF)
- EL-215BE5-C22 C — product datasheet (PDF)
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.