Skip to Content

Unit cooler EM-225AC4-C23 C

Unit cooler EM-225AC4-C23 C
Illustrative photo

Producer: Karyer · Line: EM (Low Speed Ceiling)

Product code: EM-225AC4-C23 C

Cooling capacity i
5.48 kW
Air flow
1,957 m³/h
Fin spacing
4.2 mm
Air throw
3 m
Fans
2 × ⌀250 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EM — EM - low-speed ceiling-type unit cooler
  • B
    Number of fans: 2 — Number of fans (one digit).
  • C
    Fan diameter: 25 — Ø250 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 23 — Ø250: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 1,957 m³/h
Air throw 3 m
External surface 37.4 m²
Inner volume 6.5 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 60 kg
Fans
Quantity 2
Diameter 250 mm
Speed 1,300 rpm
Power 130 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 39.0 dB(A)
Sound power 61.4 dB(A)
Energy class B
Connections
Inlet Ø12,7
Outlet Ø22
Defrost
EM-225AC4-C23 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
5.295 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 2.19 2.24 2.29 2.35 2.40 2.43 2.45 2.47 2.63 2.86 2.81 2.80 2.77 2.72
5 2.71 2.81 2.90 3.00 3.06 3.11 3.14 3.18 3.38 3.68 3.61 3.59 3.55 3.48
6 3.21 3.36 3.50 3.63 3.73 3.80 3.85 3.89 4.14 4.51 4.43 4.40 4.35 4.27
7 3.66 3.87 4.06 4.24 4.38 4.48 4.55 4.61 4.91 5.34 5.26 5.22 5.16 5.06
8 4.08 4.34 4.59 4.82 5.00 5.12 5.22 5.30 5.64 6.14 6.05 6.01 5.95 5.84
9 4.50 4.82 5.13 5.41 5.60 5.76 5.88 5.98 6.37 6.94 6.84 6.80 6.73 6.60
10 4.85 5.25 5.62 5.96 6.22 6.41 6.54 6.66 7.09 7.73 7.63 7.58 7.50 7.36

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 7.630
SC2 0 8 5.295
SC3 -18 7 4.300
SC4 -25 6 3.498
SC5 -34 6 3.242

Dimensions

Dimension drawing of EM-225AC4-C23 C
Dimension drawing
Dimensions as drawn
A 2800 mm
B 600 mm
C 366 mm
F 650 mm
G 700 mm
E 965 mm
D IN 1 x Ø12,7
D OUT 1 x Ø22
Overall [mm]
Length 2800 mm
Width 600 mm
Height 366 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.