Skip to Content

CO2 evaporator EB-DC-240AC4-A01 C

CO2 evaporator EB-DC-240AC4-A01 C
Illustrative photo

Producer: Karyer · Line: EB-DC (Economical)

Product code: EB-DC-240AC4-A01 C

Fin spacing
4.2 mm
Fans
2 × ⌀400 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EB-DC — EB-DC - economical CO₂ (R744) DX unit cooler, max. 60 barg
  • B
    Number of fans: 2 — Number of fans (one digit).
  • C
    Fan diameter: 40 — Ø400 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
External surface 38.4 m²
Inner volume 6.2 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 65 kg
Fans
Quantity 2
Diameter 400 mm
Speed 1,430 rpm
Power 320 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 83.0 dB(A)
Energy class C
Connections
Inlet Ø12,7
Outlet Ø15,9
Defrost
EB-DC-240AC4-A01 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R744, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
9.990 kW

Capacity matrix [kW]

R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 4.09 4.17 4.28 4.42 4.53 4.63 4.71 4.87 5.21 5.72 5.72 5.72 5.73 5.75
5 5.06 5.19 5.36 5.56 5.72 5.86 5.98 6.15 6.58 7.23 7.20 7.19 7.18 7.17
6 5.98 6.18 6.41 6.67 6.90 7.08 7.24 7.44 7.95 8.73 8.68 8.67 8.64 8.60
7 6.85 7.11 7.43 7.76 8.05 8.29 8.49 8.72 9.32 10.23 10.17 10.15 10.11 10.04
8 7.67 8.01 8.40 8.82 9.17 9.47 9.72 9.99 10.68 11.72 11.66 11.63 11.58 11.48
9 8.43 8.86 9.33 9.84 10.26 10.63 10.93 11.25 12.03 13.20 13.15 13.11 13.05 12.93
10 9.15 9.66 10.23 10.82 11.33 11.77 12.12 12.50 13.37 14.67 14.63 14.59 14.52 14.38

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 14.627
SC2 0 8 9.990
SC3 -18 7 7.880
SC4 -25 6 6.412
SC5 -34 6 6.027

Dimensions

Dimension drawing of EB-DC-240AC4-A01 C
Dimension drawing
Dimensions as drawn
A 1667 mm
B 650 mm
C 617 mm
F 445 mm
E1 668 mm
E 1335 mm
D IN 1 x Ø12,7
D OUT 1 x Ø15,9
Overall [mm]
Length 1667 mm
Width 650 mm
Height 606 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.