- Catalogue
- CO₂ DX evaporators
- EB-DC (Economical)
- EB-DC-240AC4-A01 C
CO2 evaporator EB-DC-240AC4-A01 C
Defrost: None
Product code: EB-DC-240AC4-A01 C
- Fin spacing
- 4.2 mm
- Fans
- 2 × ⌀400 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): EB-DC — EB-DC - economical CO₂ (R744) DX unit cooler, max. 60 barg
-
B
Number of fans: 2 — Number of fans (one digit).
-
C
Fan diameter: 40 — Ø400 mm
-
D
Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: C — 4 tube rows
-
F
Fin spacing: 4 — Fin spacing about 4 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 38.4 m² |
|---|---|
| Inner volume | 6.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 65 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø15,9 |
| EB-DC-240AC4-A01 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 9.990 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.09 | 4.17 | 4.28 | 4.42 | 4.53 | 4.63 | 4.71 | 4.87 | 5.21 | 5.72 | 5.72 | 5.72 | 5.73 | 5.75 |
| 5 | 5.06 | 5.19 | 5.36 | 5.56 | 5.72 | 5.86 | 5.98 | 6.15 | 6.58 | 7.23 | 7.20 | 7.19 | 7.18 | 7.17 |
| 6 | 5.98 | 6.18 | 6.41 | 6.67 | 6.90 | 7.08 | 7.24 | 7.44 | 7.95 | 8.73 | 8.68 | 8.67 | 8.64 | 8.60 |
| 7 | 6.85 | 7.11 | 7.43 | 7.76 | 8.05 | 8.29 | 8.49 | 8.72 | 9.32 | 10.23 | 10.17 | 10.15 | 10.11 | 10.04 |
| 8 | 7.67 | 8.01 | 8.40 | 8.82 | 9.17 | 9.47 | 9.72 | 9.99 | 10.68 | 11.72 | 11.66 | 11.63 | 11.58 | 11.48 |
| 9 | 8.43 | 8.86 | 9.33 | 9.84 | 10.26 | 10.63 | 10.93 | 11.25 | 12.03 | 13.20 | 13.15 | 13.11 | 13.05 | 12.93 |
| 10 | 9.15 | 9.66 | 10.23 | 10.82 | 11.33 | 11.77 | 12.12 | 12.50 | 13.37 | 14.67 | 14.63 | 14.59 | 14.52 | 14.38 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.627 |
| SC2 | 0 | 8 | 9.990 |
| SC3 | -18 | 7 | 7.880 |
| SC4 | -25 | 6 | 6.412 |
| SC5 | -34 | 6 | 6.027 |
Dimensions
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø15,9 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 606 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.