- Catalogue
- CO₂ DX evaporators
- EB-DC (Economical)
- EB-DC-240AC7-A01 C
CO2 evaporator EB-DC-240AC7-A01 C
Defrost: None
Product code: EB-DC-240AC7-A01 C
- Fin spacing
- 7.0 mm
- Fans
- 2 × ⌀400 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): EB-DC — EB-DC - economical CO₂ (R744) DX unit cooler, max. 60 barg
-
B
Number of fans: 2 — Number of fans (one digit).
-
C
Fan diameter: 40 — Ø400 mm
-
D
Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: C — 4 tube rows
-
F
Fin spacing: 7 — Fin spacing about 7 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 24.2 m² |
|---|---|
| Inner volume | 6.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 65 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø15,9 |
| EB-DC-240AC7-A01 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 8.051 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.33 | 3.37 | 3.44 | 3.54 | 3.62 | 3.69 | 3.76 | 3.87 | 4.15 | 4.55 | 4.54 | 4.55 | 4.55 | 4.58 |
| 5 | 4.17 | 4.24 | 4.35 | 4.48 | 4.60 | 4.70 | 4.78 | 4.91 | 5.25 | 5.76 | 5.74 | 5.74 | 5.73 | 5.73 |
| 6 | 4.98 | 5.08 | 5.23 | 5.41 | 5.57 | 5.70 | 5.81 | 5.96 | 6.37 | 6.99 | 6.95 | 6.94 | 6.92 | 6.90 |
| 7 | 5.75 | 5.90 | 6.10 | 6.32 | 6.52 | 6.69 | 6.84 | 7.01 | 7.49 | 8.21 | 8.17 | 8.15 | 8.12 | 8.07 |
| 8 | 6.48 | 6.68 | 6.94 | 7.22 | 7.47 | 7.68 | 7.85 | 8.05 | 8.60 | 9.43 | 9.39 | 9.36 | 9.32 | 9.26 |
| 9 | 7.18 | 7.44 | 7.75 | 8.10 | 8.39 | 8.64 | 8.86 | 9.09 | 9.72 | 10.65 | 10.60 | 10.57 | 10.53 | 10.44 |
| 10 | 7.85 | 8.17 | 8.54 | 8.95 | 9.30 | 9.60 | 9.85 | 10.12 | 10.82 | 11.86 | 11.82 | 11.78 | 11.73 | 11.63 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.815 |
| SC2 | 0 | 8 | 8.051 |
| SC3 | -18 | 7 | 6.407 |
| SC4 | -25 | 6 | 5.232 |
| SC5 | -34 | 6 | 5.001 |
Dimensions
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø15,9 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 606 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.