Skip to Content

Compressor rack BHSR-6P-ZB76

Compressor rack BHSR-6P-ZB76
Illustrative photo

Producer: Albassem BRI · Line: Hatshepsut ScrollRack MT

Product code: BHSR-6P-ZB76

Refrigerating capacity i
104.50 kW
Absorbed power
48.90 kW
COP
2.14
Compressors
6 × scroll compressors
Receiver
120 l

Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.

Model nomenclature

How to read the code of this model.

  • A
    Series: BHSR — Hatshepsut ScrollRack
  • B
    Number of compressors: 6 — Number of identical compressors on the rack (5 to 6).
  • C
    Application: P — Medium / high temperature
  • D
    Compressor model: ZB76 — Model of the compressors fitted (all compressors of a rack are the same model); an 'EVI' tail marks enhanced vapour injection.

Data

Rack
ApplicationMedium temperature (MT)
Compressors6 × scroll compressors
Liquid receiver 120 l
Net weight 980 kg
Electrical
Max. current 108.0 A
Starting current 208.0 A
Connections
Suction 3"1/8
Liquid 1"3/8
Discharge 2"1/8
Liquid set
L / W / H 714/455/1834 mm
Weight 130 kg

Performance

Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.

R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)

Refrigerating capacity
104.50 kW
Absorbed power
48.90 kW
COP
2.14
Current
90.6 A
Heat rejection
153.40 kW

Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.

Standard points

Te [°C] Tc [°C] Refrigerating capacity [kW] Absorbed power [kW] COP Current [A]
-10 40 114.30 44.00 2.60 84.5
-10 45 104.50 48.90 2.14 90.6

Evaporating × condensing temperature (dew points)

R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.

Capacity [kW]

Capacity [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -25-20-15-10-505
20 78.60 98.00 121.20 148.70 180.90 218.30 not rated
25 74.20 92.70 114.70 140.70 171.10 206.30 246.70
30 69.40 87.00 107.80 132.30 160.90 194.00 232.10
35 64.00 80.80 100.50 123.50 150.30 181.40 217.20
40 58.10 74.10 92.70 114.30 139.40 168.50 202.00
45 51.40 66.70 84.30 104.50 127.90 155.10 186.40
50 not rated 58.70 75.20 94.10 115.90 141.20 170.40
55 not rated 50.00 65.60 83.20 103.40 126.80 154.00

Power [kW]

Power [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -25-20-15-10-505
20 27.70 28.30 28.90 29.50 30.10 30.70 not rated
25 30.70 31.40 31.90 32.50 33.00 33.60 34.20
30 34.20 34.80 35.30 35.80 36.30 36.90 37.40
35 38.10 38.60 39.20 39.60 40.10 40.50 41.00
40 42.50 43.10 43.50 44.00 44.40 44.70 45.10
45 47.60 48.10 48.50 48.90 49.20 49.50 49.80
50 not rated 53.80 54.20 54.50 54.70 54.90 55.10
55 not rated 60.30 60.60 60.80 61.00 61.10 61.20

COP

COP: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -25-20-15-10-505
20 2.84 3.46 4.19 5.04 6.01 7.11 not rated
25 2.42 2.95 3.60 4.33 5.18 6.14 7.21
30 2.03 2.50 3.05 3.70 4.43 5.26 6.21
35 1.68 2.09 2.56 3.12 3.75 4.48 5.30
40 1.37 1.72 2.13 2.60 3.14 3.77 4.48
45 1.08 1.39 1.74 2.14 2.60 3.13 3.74
50 not rated 1.09 1.39 1.73 2.12 2.57 3.09
55 not rated 0.83 1.08 1.37 1.70 2.08 2.52

Dimensions

Dimension drawing of BHSR-6P-ZB76
Dimension drawing
Dimensions as drawn
L 3715 mm
P 800 mm
H 1500 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.