EA-130BE8-C01 C
2.77 kW
Defrost: None
Product code: EA-135AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,560 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 7.0 m² |
| Inner volume | 3.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 29 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-135AC10-C01 C | None |
|---|---|
| EA-135AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.99 | 0.97 | 0.96 | 0.95 | 0.94 | 0.92 | 0.91 | 0.91 | 0.96 | 1.04 | 1.01 | 1.00 | 0.98 | 0.96 |
| 5 | 1.35 | 1.34 | 1.34 | 1.33 | 1.32 | 1.30 | 1.29 | 1.29 | 1.37 | 1.47 | 1.43 | 1.41 | 1.39 | 1.35 |
| 6 | 1.71 | 1.72 | 1.74 | 1.75 | 1.74 | 1.73 | 1.71 | 1.71 | 1.81 | 1.95 | 1.89 | 1.87 | 1.84 | 1.79 |
| 7 | 2.07 | 2.10 | 2.14 | 2.17 | 2.18 | 2.18 | 2.17 | 2.17 | 2.29 | 2.47 | 2.40 | 2.37 | 2.32 | 2.26 |
| 8 | 2.41 | 2.48 | 2.55 | 2.61 | 2.63 | 2.65 | 2.64 | 2.65 | 2.80 | 3.03 | 2.93 | 2.90 | 2.84 | 2.76 |
| 9 | 2.72 | 2.82 | 2.93 | 3.02 | 3.08 | 3.12 | 3.12 | 3.14 | 3.33 | 3.60 | 3.50 | 3.45 | 3.39 | 3.29 |
| 10 | 2.99 | 3.13 | 3.26 | 3.39 | 3.47 | 3.52 | 3.55 | 3.60 | 3.82 | 4.15 | 4.06 | 4.02 | 3.95 | 3.83 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.064 |
| SC2 | 0 | 8 | 2.648 |
| SC3 | -18 | 7 | 2.179 |
| SC4 | -25 | 6 | 1.735 |
| SC5 | -34 | 6 | 1.718 |
| A | 857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.