EA-230AC4-C05 C
4.25 kW
Defrost: None
Product code: EA-135AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,167 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 14.3 m² |
| Inner volume | 4.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-135AE7-C01 C | None |
|---|---|
| EA-135AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.60 | 1.58 | 1.58 | 1.57 | 1.57 | 1.55 | 1.54 | 1.58 | 1.68 | 1.82 | 1.78 | 1.76 | 1.74 | 1.71 |
| 5 | 2.13 | 2.13 | 2.13 | 2.14 | 2.13 | 2.12 | 2.09 | 2.12 | 2.26 | 2.44 | 2.38 | 2.36 | 2.33 | 2.29 |
| 6 | 2.65 | 2.68 | 2.71 | 2.74 | 2.74 | 2.73 | 2.69 | 2.72 | 2.88 | 3.12 | 3.02 | 2.98 | 2.94 | 2.86 |
| 7 | 3.17 | 3.22 | 3.29 | 3.35 | 3.37 | 3.37 | 3.33 | 3.36 | 3.55 | 3.84 | 3.71 | 3.66 | 3.59 | 3.47 |
| 8 | 3.64 | 3.76 | 3.87 | 3.97 | 4.02 | 4.02 | 4.00 | 4.02 | 4.25 | 4.59 | 4.44 | 4.38 | 4.28 | 4.13 |
| 9 | 4.09 | 4.26 | 4.42 | 4.56 | 4.65 | 4.68 | 4.67 | 4.70 | 4.97 | 5.37 | 5.20 | 5.12 | 5.01 | 4.82 |
| 10 | 4.47 | 4.70 | 4.91 | 5.09 | 5.21 | 5.26 | 5.28 | 5.34 | 5.67 | 6.14 | 5.96 | 5.88 | 5.75 | 5.53 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.961 |
| SC2 | 0 | 8 | 4.018 |
| SC3 | -18 | 7 | 3.361 |
| SC4 | -25 | 6 | 2.708 |
| SC5 | -34 | 6 | 2.658 |
| A | 857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.