EA-330AC7-C05 C
5.83 kW
Defrost: None
Product code: EA-145AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,428 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 14.8 m² |
| Inner volume | 5.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-145AC8-C01 C | None |
|---|---|
| EA-145AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.03 | 2.01 | 2.01 | 2.00 | 1.98 | 1.96 | 1.93 | 1.93 | 2.04 | 2.19 | 2.13 | 2.10 | 2.07 | 2.02 |
| 5 | 2.72 | 2.76 | 2.80 | 2.82 | 2.82 | 2.80 | 2.76 | 2.78 | 2.94 | 3.17 | 3.07 | 3.03 | 2.98 | 2.90 |
| 6 | 3.42 | 3.52 | 3.62 | 3.68 | 3.72 | 3.72 | 3.69 | 3.72 | 3.94 | 4.25 | 4.11 | 4.07 | 4.00 | 3.90 |
| 7 | 4.04 | 4.22 | 4.38 | 4.53 | 4.63 | 4.68 | 4.67 | 4.71 | 4.99 | 5.39 | 5.23 | 5.17 | 5.08 | 4.94 |
| 8 | 4.56 | 4.81 | 5.05 | 5.23 | 5.37 | 5.47 | 5.52 | 5.60 | 5.95 | 6.47 | 6.34 | 6.28 | 6.20 | 6.07 |
| 9 | 5.03 | 5.37 | 5.65 | 5.92 | 6.12 | 6.25 | 6.33 | 6.43 | 6.84 | 7.44 | 7.29 | 7.23 | 7.14 | 6.98 |
| 10 | 5.47 | 5.86 | 6.25 | 6.60 | 6.86 | 7.03 | 7.15 | 7.27 | 7.73 | 8.42 | 8.26 | 8.19 | 8.09 | 7.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.263 |
| SC2 | 0 | 8 | 5.598 |
| SC3 | -18 | 7 | 4.578 |
| SC4 | -25 | 6 | 3.616 |
| SC5 | -34 | 6 | 3.443 |
| A | 1067 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E | 735 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1067 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.