EA-150AE6-C09 C
11.68 kW
Defrost: None
Product code: EA-163EC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,336 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 66.8 m² |
| Inner volume | 13.6 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 105 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 74.1 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-163EC4-C01 C | None |
|---|---|
| EA-163EC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.43 | 4.41 | 4.41 | 4.44 | 4.44 | 4.43 | 4.42 | 4.51 | 4.78 | 5.18 | 5.09 | 5.05 | 5.00 | 4.93 |
| 5 | 5.81 | 5.85 | 5.90 | 5.94 | 5.95 | 5.94 | 5.90 | 5.98 | 6.36 | 6.89 | 6.74 | 6.69 | 6.62 | 6.52 |
| 6 | 7.17 | 7.31 | 7.44 | 7.55 | 7.59 | 7.59 | 7.54 | 7.61 | 8.07 | 8.73 | 8.51 | 8.43 | 8.32 | 8.16 |
| 7 | 8.45 | 8.74 | 8.95 | 9.16 | 9.27 | 9.30 | 9.27 | 9.34 | 9.90 | 10.71 | 10.41 | 10.30 | 10.14 | 9.90 |
| 8 | 9.57 | 9.99 | 10.37 | 10.71 | 10.93 | 11.06 | 11.08 | 11.16 | 11.83 | 12.80 | 12.44 | 12.31 | 12.10 | 11.77 |
| 9 | 10.57 | 11.14 | 11.66 | 12.11 | 12.41 | 12.59 | 12.68 | 12.82 | 13.61 | 14.78 | 14.45 | 14.31 | 14.11 | 13.74 |
| 10 | 11.49 | 12.23 | 12.90 | 13.48 | 13.88 | 14.12 | 14.26 | 14.42 | 15.31 | 16.63 | 16.26 | 16.10 | 15.86 | 15.46 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.255 |
| SC2 | 0 | 8 | 11.157 |
| SC3 | -18 | 7 | 9.216 |
| SC4 | -25 | 6 | 7.440 |
| SC5 | -34 | 6 | 7.207 |
| A | 1215 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E | 835 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1215 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.