Skip to Content

Unit cooler EA-191AG10-C04 C

Unit cooler EA-191AG10-C04 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-191AG10-C04 C

Cooling capacity i
48.05 kW
Air flow
28,359 m³/h
Fin spacing
10.0 mm
Air throw
46 m
Fans
1 × ⌀910 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 1 — Number of fans (one digit).
  • C
    Fan diameter: 91 — Ø910 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 04 — Ø910: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 28,359 m³/h
Air throw 46 m
External surface 195.3 m²
Inner volume 83.5 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 399 kg
Fans
Quantity 1
Diameter 910 mm
Speed 840 rpm
Power 2,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 90.0 dB(A)
Energy class C
Connections
Inlet Ø42
Outlet Ø66,7
Defrost
EA-191AG10-C04 C None
EA-191AG10-C04 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
45.932 kW
Low speed (Y)
37.242 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 19.38 18.95 18.72 18.62 18.48 18.32 18.15 18.36 19.47 21.05 20.56 20.38 20.13 19.75
5 25.69 25.33 25.15 25.09 24.93 24.71 24.43 24.57 26.04 28.13 27.39 27.13 26.76 26.23
6 32.15 31.88 31.87 31.95 31.84 31.59 31.25 31.32 33.15 35.77 34.71 34.32 33.77 32.94
7 38.40 38.54 38.77 39.05 39.02 38.82 38.46 38.48 40.70 43.91 42.52 42.00 41.24 40.06
8 44.42 45.01 45.61 46.19 46.39 46.29 45.96 45.93 48.58 52.43 50.74 50.08 49.13 47.58
9 50.15 51.28 52.35 53.16 53.65 53.74 53.49 53.54 56.63 61.13 59.21 58.45 57.32 55.48
10 55.54 57.08 58.70 60.13 60.91 61.23 61.14 61.28 64.85 70.03 67.95 67.08 65.79 63.64

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 16.27 15.90 15.73 15.68 15.60 15.50 15.39 15.64 16.63 18.04 17.69 17.56 17.37 17.08
5 21.42 21.05 20.88 20.84 20.73 20.57 20.38 20.57 21.83 23.63 23.04 22.84 22.56 22.15
6 26.65 26.36 26.26 26.28 26.19 26.00 25.73 25.86 27.39 29.60 28.76 28.45 28.01 27.35
7 31.95 31.72 31.77 31.91 31.87 31.68 31.37 31.44 33.27 35.93 34.81 34.39 33.78 32.82
8 37.07 37.15 37.38 37.67 37.69 37.54 37.23 37.24 39.39 42.52 41.16 40.62 39.83 38.54
9 42.01 42.42 42.92 43.44 43.62 43.52 43.20 43.22 45.70 49.30 47.73 47.08 46.11 44.48
10 46.76 47.57 48.39 49.19 49.52 49.55 49.28 49.33 52.10 56.21 54.46 53.70 52.56 50.62

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 67.95054.457
SC2 0 8 45.93237.242
SC3 -18 7 39.07831.912
SC4 -25 6 31.87326.262
SC5 -34 6 32.14626.617

Dimensions

Dimension drawing of EA-191AG10-C04 C
Dimension drawing
Dimensions as drawn
A 2038 mm
C 1587 mm
F 1032 mm
G 1150 mm
E1 835 mm
E2 800 mm
E 1635 mm
H 1334 mm
I 1750 mm
D IN 1 x Ø42
D OUT 1 x Ø66,7
Overall [mm]
Length 2038 mm
Width 1334 mm
Height 1750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.