EA-330AE6-C05 C
7.36 kW
Defrost: None
Product code: EA-240AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,713 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 17.9 m² |
| Inner volume | 8.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 58 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-240AC10-C01 C | None |
|---|---|
| EA-240AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.62 | 2.60 | 2.60 | 2.59 | 2.57 | 2.55 | 2.51 | 2.53 | 2.67 | 2.87 | 2.79 | 2.75 | 2.71 | 2.64 |
| 5 | 3.49 | 3.53 | 3.58 | 3.61 | 3.62 | 3.60 | 3.56 | 3.59 | 3.80 | 4.10 | 3.98 | 3.94 | 3.88 | 3.78 |
| 6 | 4.36 | 4.47 | 4.57 | 4.67 | 4.72 | 4.73 | 4.71 | 4.74 | 5.02 | 5.43 | 5.27 | 5.21 | 5.12 | 4.99 |
| 7 | 5.15 | 5.36 | 5.56 | 5.73 | 5.84 | 5.89 | 5.89 | 5.94 | 6.30 | 6.83 | 6.64 | 6.57 | 6.46 | 6.28 |
| 8 | 5.83 | 6.13 | 6.40 | 6.65 | 6.81 | 6.93 | 7.00 | 7.10 | 7.55 | 8.21 | 8.05 | 7.97 | 7.85 | 7.65 |
| 9 | 6.45 | 6.84 | 7.17 | 7.50 | 7.74 | 7.91 | 8.01 | 8.14 | 8.66 | 9.42 | 9.25 | 9.18 | 9.06 | 8.87 |
| 10 | 7.02 | 7.48 | 7.93 | 8.35 | 8.66 | 8.88 | 9.03 | 9.18 | 9.77 | 10.64 | 10.46 | 10.38 | 10.25 | 10.03 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.460 |
| SC2 | 0 | 8 | 7.100 |
| SC3 | -18 | 7 | 5.780 |
| SC4 | -25 | 6 | 4.567 |
| SC5 | -34 | 6 | 4.387 |
| A | 1467 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1467 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |