EA-163EE10-C11 C
16.02 kW
Defrost: None
Product code: EA-245AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,957 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 53.3 m² |
| Inner volume | 11.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 81 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-245AC4-C01 C | None |
|---|---|
| EA-245AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.86 | 5.98 | 6.09 | 6.17 | 6.19 | 6.17 | 6.11 | 6.25 | 6.62 | 7.15 | 6.97 | 6.91 | 6.81 | 6.68 |
| 5 | 7.66 | 7.99 | 8.27 | 8.49 | 8.60 | 8.61 | 8.56 | 8.70 | 9.25 | 10.01 | 9.76 | 9.67 | 9.54 | 9.36 |
| 6 | 9.13 | 9.63 | 10.08 | 10.40 | 10.66 | 10.81 | 10.88 | 11.08 | 11.79 | 12.82 | 12.56 | 12.46 | 12.31 | 12.09 |
| 7 | 10.44 | 11.07 | 11.70 | 12.26 | 12.65 | 12.89 | 13.01 | 13.24 | 14.09 | 15.32 | 14.99 | 14.86 | 14.67 | 14.35 |
| 8 | 11.54 | 12.46 | 13.31 | 14.07 | 14.61 | 14.96 | 15.15 | 15.43 | 16.42 | 17.86 | 17.48 | 17.32 | 17.08 | 16.67 |
| 9 | ≈ 12.59 | 13.75 | 14.83 | 15.80 | 16.52 | 17.02 | 17.30 | 17.64 | 18.77 | 20.44 | 20.01 | 19.82 | 19.54 | 19.04 |
| 10 | 13.53 | 14.93 | 16.26 | 17.47 | 18.38 | 19.03 | 19.43 | 19.85 | 21.13 | 23.02 | 22.58 | 22.36 | 22.03 | 21.46 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.576 |
| SC2 | 0 | 8 | 15.430 |
| SC3 | -18 | 7 | 12.435 |
| SC4 | -25 | 6 | 10.075 |
| SC5 | -34 | 6 | 9.249 |
| A | 1767 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 1767 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.