EA-535AE6-C01 C
22.18 kW
Defrost: None
Product code: EA-250AE7-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,756 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 64.9 m² |
| Inner volume | 22.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 114 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-250AE7-C09 C | None |
|---|---|
| EA-250AE7-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.17 | 8.10 | 8.06 | 8.05 | 7.99 | 7.90 | 7.79 | 7.94 | 8.40 | 9.06 | 8.82 | 8.73 | 8.61 | 8.42 |
| 5 | 10.89 | 10.96 | 11.04 | 11.12 | 11.09 | 11.00 | 10.86 | 10.98 | 11.65 | 12.58 | 12.23 | 12.11 | 11.94 | 11.71 |
| 6 | 13.60 | 13.88 | 14.13 | 14.32 | 14.40 | 14.36 | 14.22 | 14.33 | 15.19 | 16.39 | 15.87 | 15.68 | 15.41 | 15.01 |
| 7 | 16.09 | 16.62 | 17.13 | 17.58 | 17.80 | 17.85 | 17.74 | 17.87 | 18.92 | 20.45 | 19.80 | 19.55 | 19.17 | 18.58 |
| 8 | 18.21 | 18.99 | 19.72 | 20.37 | 20.72 | 20.97 | 21.05 | 21.30 | 22.61 | 24.55 | 23.89 | 23.58 | 23.13 | 22.39 |
| 9 | 20.18 | 21.25 | 22.12 | 22.99 | 23.58 | 23.93 | 24.09 | 24.39 | 25.89 | 28.10 | 27.43 | 27.14 | 26.70 | 25.96 |
| 10 | 22.00 | 23.26 | 24.52 | 25.63 | 26.40 | 26.89 | 27.14 | 27.50 | 29.20 | 31.70 | 30.97 | 30.64 | 30.14 | 29.28 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.970 |
| SC2 | 0 | 8 | 21.296 |
| SC3 | -18 | 7 | 17.692 |
| SC4 | -25 | 6 | 14.131 |
| SC5 | -34 | 6 | 13.674 |
| A | 2087 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2087 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.