EA-345AE8-C01 C
23.14 kW
Defrost: None
Product code: EA-250AG10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,367 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 63.3 m² |
| Inner volume | 30.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 140 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-250AG10-C09 C | None |
|---|---|
| EA-250AG10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.80 | 8.65 | 8.57 | 8.52 | 8.44 | 8.33 | 8.21 | 8.37 | 8.88 | 9.58 | 9.32 | 9.23 | 9.10 | 8.90 |
| 5 | 11.75 | 11.69 | 11.69 | 11.70 | 11.64 | 11.52 | 11.35 | 11.48 | 12.18 | 13.15 | 12.77 | 12.64 | 12.47 | 12.22 |
| 6 | 14.66 | 14.76 | 14.89 | 15.03 | 15.03 | 14.94 | 14.76 | 14.86 | 15.74 | 16.99 | 16.43 | 16.22 | 15.94 | 15.50 |
| 7 | 17.54 | 17.84 | 18.09 | 18.39 | 18.51 | 18.48 | 18.33 | 18.42 | 19.49 | 21.05 | 20.33 | 20.06 | 19.65 | 18.99 |
| 8 | 20.21 | 20.77 | 21.30 | 21.78 | 22.04 | 22.08 | 21.98 | 22.08 | 23.37 | 25.25 | 24.43 | 24.09 | 23.58 | 22.73 |
| 9 | 22.64 | 23.45 | 24.23 | 24.95 | 25.40 | 25.66 | 25.65 | 25.81 | 27.33 | 29.51 | 28.61 | 28.22 | 27.61 | 26.59 |
| 10 | 24.84 | 25.93 | 26.96 | 27.90 | 28.41 | 28.78 | 28.93 | 29.25 | 31.03 | 33.63 | 32.80 | 32.40 | 31.71 | 30.53 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 32.803 |
| SC2 | 0 | 8 | 22.082 |
| SC3 | -18 | 7 | 18.459 |
| SC4 | -25 | 6 | 14.892 |
| SC5 | -34 | 6 | 14.697 |
| A | 2087 mm |
|---|---|
| B | 740 mm |
| C | 685 mm |
| F | 545 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2087 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.