EA-440AG4-C01 C
26.78 kW
Defrost: None
Product code: EA-250AG6-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,407 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 99.3 m² |
| Inner volume | 30.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 146 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.6 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-250AG6-C09 C | None |
|---|---|
| EA-250AG6-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.45 | 10.39 | 10.39 | 10.42 | 10.39 | 10.31 | 10.19 | 10.47 | 11.16 | 12.11 | 11.87 | 11.80 | 11.68 | 11.47 |
| 5 | 13.66 | 13.75 | 13.86 | 13.98 | 13.99 | 13.91 | 13.74 | 13.98 | 14.85 | 16.09 | 15.65 | 15.50 | 15.31 | 15.04 |
| 6 | 16.86 | 17.09 | 17.39 | 17.67 | 17.77 | 17.72 | 17.54 | 17.73 | 18.79 | 20.33 | 19.67 | 19.43 | 19.08 | 18.54 |
| 7 | 19.84 | 20.41 | 20.95 | 21.42 | 21.64 | 21.64 | 21.48 | 21.65 | 22.92 | 24.79 | 23.95 | 23.62 | 23.12 | 22.33 |
| 8 | 22.55 | 23.41 | 24.22 | 24.94 | 25.39 | 25.60 | 25.50 | 25.67 | 27.14 | 29.34 | 28.38 | 27.98 | 27.36 | 26.34 |
| 9 | 24.99 | 26.17 | 27.25 | 28.10 | 28.73 | 29.03 | 29.10 | 29.41 | 31.19 | 33.77 | 32.84 | 32.43 | 31.71 | 30.47 |
| 10 | 27.25 | 28.78 | 30.04 | 31.27 | 32.07 | 32.53 | 32.67 | 33.03 | 35.02 | 37.91 | 36.90 | 36.42 | 35.69 | 34.42 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.896 |
| SC2 | 0 | 8 | 25.674 |
| SC3 | -18 | 7 | 21.533 |
| SC4 | -25 | 6 | 17.394 |
| SC5 | -34 | 6 | 16.946 |
| A | 2087 mm |
|---|---|
| B | 740 mm |
| C | 685 mm |
| F | 545 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2087 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.