EA-191AG4-C04 C
62.01 kW
Defrost: None
Product code: EA-263GE4-C13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 34,910 m³/h |
|---|---|
| Air throw | 45 m |
| External surface | 325.8 m² |
| Inner volume | 67.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 336 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 90.9 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-263GE4-C13 C | None |
|---|---|
| EA-263GE4-C13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 24.05 | 23.88 | 23.85 | 23.93 | 23.92 | 23.85 | 23.76 | 24.03 | 25.50 | 27.63 | 27.08 | 26.87 | 26.59 | 26.16 |
| 5 | 31.60 | 31.71 | 31.89 | 32.11 | 32.10 | 32.01 | 31.83 | 32.03 | 33.98 | 36.77 | 35.92 | 35.62 | 35.19 | 34.56 |
| 6 | 38.93 | 39.59 | 40.20 | 40.75 | 40.95 | 40.83 | 40.63 | 40.78 | 43.21 | 46.72 | 45.51 | 45.06 | 44.43 | 43.46 |
| 7 | 45.89 | 47.05 | 48.29 | 49.36 | 49.92 | 50.09 | 49.98 | 50.14 | 53.11 | 57.42 | 55.85 | 55.25 | 54.38 | 53.01 |
| 8 | 51.58 | 53.58 | 55.43 | 57.09 | 58.18 | 58.83 | 59.15 | 59.64 | 63.31 | 68.65 | 66.79 | 66.06 | 64.98 | 63.24 |
| 9 | 57.03 | 59.81 | 62.34 | 64.57 | 66.06 | 66.99 | 67.48 | 68.05 | 72.25 | 78.39 | 76.67 | 75.96 | 74.91 | 73.17 |
| 10 | 62.09 | 65.73 | 69.03 | 71.91 | 73.89 | 75.13 | 75.84 | 76.56 | 81.29 | 88.21 | 86.31 | 85.50 | 84.29 | 82.26 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.83 | 20.62 | 20.58 | 20.65 | 20.66 | 20.63 | 20.57 | 20.92 | 22.26 | 24.17 | 23.76 | 23.60 | 23.37 | 23.04 |
| 5 | 27.22 | 27.07 | 27.15 | 27.31 | 27.33 | 27.25 | 27.10 | 27.43 | 29.13 | 31.57 | 30.88 | 30.65 | 30.31 | 29.82 |
| 6 | 33.55 | 33.78 | 34.08 | 34.40 | 34.49 | 34.38 | 34.17 | 34.43 | 36.52 | 39.53 | 38.52 | 38.15 | 37.62 | 36.83 |
| 7 | 39.68 | 40.39 | 41.06 | 41.68 | 41.85 | 41.85 | 41.63 | 41.84 | 44.33 | 47.93 | 46.59 | 46.08 | 45.33 | 44.16 |
| 8 | 45.51 | 46.61 | 47.80 | 48.84 | 49.39 | 49.54 | 49.38 | 49.57 | 52.50 | 56.78 | 55.12 | 54.47 | 53.50 | 51.96 |
| 9 | 50.43 | 52.24 | 53.94 | 55.49 | 56.48 | 57.00 | 57.19 | 57.54 | 60.93 | 65.89 | 63.99 | 63.21 | 62.04 | 60.13 |
| 10 | 55.12 | 57.59 | 59.85 | 61.86 | 63.14 | 63.90 | 64.20 | 64.74 | 68.67 | 74.43 | 72.64 | 71.86 | 70.70 | 68.54 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 86.306 | 72.639 |
| SC2 | 0 | 8 | 59.640 | 49.573 |
| SC3 | -18 | 7 | 49.634 | 41.825 |
| SC4 | -25 | 6 | 40.199 | 34.076 |
| SC5 | -34 | 6 | 39.122 | 33.642 |
| A | 3015 mm |
|---|---|
| B | 1000 mm |
| C | 1185 mm |
| F | 960 mm |
| G | 1030 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3015 mm |
|---|---|
| Width | 1110 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.