EA-140AG8-C01 C
5.64 kW
Defrost: None
Product code: EA-330AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,061 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 18.4 m² |
| Inner volume | 7.1 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 48 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AC8-C01 C | None |
|---|---|
| EA-330AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.11 | 2.07 | 2.05 | 2.04 | 2.03 | 2.01 | 1.99 | 2.02 | 2.13 | 2.30 | 2.25 | 2.23 | 2.20 | 2.16 |
| 5 | 2.83 | 2.81 | 2.81 | 2.81 | 2.80 | 2.77 | 2.74 | 2.77 | 2.93 | 3.17 | 3.09 | 3.06 | 3.02 | 2.97 |
| 6 | 3.56 | 3.58 | 3.60 | 3.63 | 3.63 | 3.61 | 3.57 | 3.60 | 3.81 | 4.12 | 4.00 | 3.95 | 3.89 | 3.80 |
| 7 | 4.29 | 4.35 | 4.40 | 4.47 | 4.50 | 4.49 | 4.46 | 4.49 | 4.75 | 5.13 | 4.97 | 4.91 | 4.83 | 4.69 |
| 8 | 4.97 | 5.09 | 5.22 | 5.33 | 5.39 | 5.40 | 5.39 | 5.41 | 5.73 | 6.20 | 6.01 | 5.94 | 5.83 | 5.66 |
| 9 | 5.59 | 5.78 | 5.97 | 6.14 | 6.26 | 6.32 | 6.33 | 6.36 | 6.74 | 7.30 | 7.09 | 7.00 | 6.88 | 6.67 |
| 10 | 6.15 | 6.41 | 6.65 | 6.88 | 7.01 | 7.11 | 7.17 | 7.25 | 7.70 | 8.36 | 8.18 | 8.09 | 7.95 | 7.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.175 |
| SC2 | 0 | 8 | 5.413 |
| SC3 | -18 | 7 | 4.485 |
| SC4 | -25 | 6 | 3.600 |
| SC5 | -34 | 6 | 3.569 |
| A | 1657 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 451 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.