Skip to Content

Unit cooler EA-363EG10-C01 C

Unit cooler EA-363EG10-C01 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-363EG10-C01 C

Cooling capacity i
41.01 kW
Air flow
23,112 m³/h
Fin spacing
10.0 mm
Air throw
22 m
Fans
3 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: E — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole; Ø630: 230V/1Ph/50Hz, 6-pole; Ø800: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 23,112 m³/h
Air throw 22 m
External surface 195.3 m²
Inner volume 79.6 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 340 kg
Fans
Quantity 3
Diameter 630 mm
Speed 860 rpm
Power 1,800 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 79.7 dB(A)
Energy class C
Connections
Inlet Ø35
Outlet Ø54
Defrost
EA-363EG10-C01 C None
EA-363EG10-C01 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
39.324 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 16.15 16.13 16.17 16.24 16.21 16.12 15.97 16.29 17.34 18.79 18.39 18.22 17.99 17.64
5 21.00 21.13 21.38 21.62 21.68 21.59 21.40 21.68 23.02 24.92 24.25 24.02 23.69 23.22
6 25.58 26.16 26.70 27.18 27.38 27.34 27.15 27.40 29.05 31.42 30.48 30.13 29.62 28.83
7 29.89 30.94 31.89 32.70 33.13 33.17 33.05 33.29 35.26 38.15 36.99 36.53 35.84 34.72
8 33.89 35.49 36.72 37.95 38.69 39.03 39.04 39.32 41.67 45.10 43.76 43.20 42.35 40.95
9 37.55 39.43 41.31 42.98 44.07 44.74 45.00 45.41 48.14 52.12 50.65 50.00 49.02 47.36
10 40.55 43.17 45.57 47.68 49.10 50.00 50.44 51.08 54.22 58.81 57.41 56.77 55.76 53.85

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 57.413
SC2 0 8 39.324
SC3 -18 7 32.911
SC4 -25 6 26.703
SC5 -34 6 25.741

Dimensions

Dimension drawing of EA-363EG10-C01 C
Dimension drawing
Dimensions as drawn
A 2815 mm
B 1100 mm
C 1190 mm
F 1060 mm
E1 818 mm
E2 800 mm
E 2435 mm
D IN 1 x Ø35
D OUT 1 x Ø54
Overall [mm]
Length 2815 mm
Width 1100 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.