EA-530AC10-C05 C
8.08 kW
Defrost: None
Product code: EA-430AC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,741 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 27.8 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC7-C05 C | None |
|---|---|
| EA-430AC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.06 | 3.03 | 3.02 | 3.02 | 3.01 | 2.99 | 2.97 | 3.03 | 3.23 | 3.49 | 3.41 | 3.39 | 3.35 | 3.29 |
| 5 | 4.04 | 4.05 | 4.07 | 4.10 | 4.11 | 4.09 | 4.05 | 4.10 | 4.36 | 4.72 | 4.60 | 4.56 | 4.51 | 4.43 |
| 6 | 5.00 | 5.08 | 5.16 | 5.23 | 5.26 | 5.26 | 5.22 | 5.27 | 5.59 | 6.05 | 5.87 | 5.81 | 5.71 | 5.57 |
| 7 | 5.96 | 6.11 | 6.25 | 6.39 | 6.45 | 6.47 | 6.44 | 6.50 | 6.88 | 7.45 | 7.23 | 7.14 | 7.01 | 6.80 |
| 8 | 6.82 | 7.06 | 7.29 | 7.51 | 7.65 | 7.71 | 7.70 | 7.76 | 8.23 | 8.91 | 8.65 | 8.54 | 8.38 | 8.12 |
| 9 | 7.58 | 7.91 | 8.23 | 8.51 | 8.68 | 8.80 | 8.86 | 8.97 | 9.52 | 10.34 | 10.10 | 9.97 | 9.79 | 9.48 |
| 10 | 8.29 | 8.73 | 9.10 | 9.46 | 9.71 | 9.87 | 9.96 | 10.09 | 10.72 | 11.63 | 11.38 | 11.26 | 11.08 | 10.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.376 |
| SC2 | 0 | 8 | 7.761 |
| SC3 | -18 | 7 | 6.422 |
| SC4 | -25 | 6 | 5.155 |
| SC5 | -34 | 6 | 5.023 |
| A | 2107 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 437.5 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.