EA-163FD10-C08 C
14.39 kW
Defrost: None
Product code: EA-440AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,423 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 35.8 m² |
| Inner volume | 16.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 102 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-440AC10-C01 C | None |
|---|---|
| EA-440AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.13 | 5.15 | 5.18 | 5.20 | 5.18 | 5.14 | 5.08 | 5.12 | 5.41 | 5.83 | 5.65 | 5.59 | 5.49 | 5.35 |
| 5 | 6.76 | 6.92 | 7.06 | 7.19 | 7.24 | 7.24 | 7.19 | 7.25 | 7.69 | 8.31 | 8.08 | 8.00 | 7.88 | 7.70 |
| 6 | 8.35 | 8.68 | 8.97 | 9.23 | 9.37 | 9.44 | 9.44 | 9.53 | 10.12 | 10.95 | 10.65 | 10.54 | 10.37 | 10.12 |
| 7 | 9.75 | 10.23 | 10.69 | 11.10 | 11.40 | 11.56 | 11.68 | 11.86 | 12.61 | 13.67 | 13.35 | 13.22 | 13.03 | 12.71 |
| 8 | 10.95 | 11.62 | 12.25 | 12.74 | 13.15 | 13.44 | 13.62 | 13.85 | 14.74 | 16.05 | 15.76 | 15.64 | 15.46 | 15.15 |
| 9 | 12.05 | 12.84 | 13.64 | 14.37 | 14.91 | 15.30 | 15.56 | 15.84 | 16.87 | 18.39 | 18.08 | 17.95 | 17.74 | 17.38 |
| 10 | 13.05 | 14.04 | 15.04 | 15.95 | 16.64 | 17.15 | 17.50 | 17.84 | 19.01 | 20.73 | 20.42 | 20.27 | 20.04 | 19.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.417 |
| SC2 | 0 | 8 | 13.847 |
| SC3 | -18 | 7 | 11.234 |
| SC4 | -25 | 6 | 8.973 |
| SC5 | -34 | 6 | 8.433 |
| A | 2567 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2567 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.