EA-263EC4-C06 C
23.79 kW
Defrost: None
Product code: EA-440AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,365 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 117.2 m² |
| Inner volume | 24.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 132 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-440AE4-C01 C | None |
|---|---|
| EA-440AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.27 | 9.21 | 9.21 | 9.25 | 9.24 | 9.19 | 9.10 | 9.40 | 10.04 | 10.92 | 10.75 | 10.71 | 10.61 | 10.46 |
| 5 | 12.14 | 12.20 | 12.29 | 12.39 | 12.39 | 12.31 | 12.17 | 12.43 | 13.23 | 14.35 | 13.99 | 13.87 | 13.73 | 13.53 |
| 6 | 15.04 | 15.27 | 15.46 | 15.68 | 15.75 | 15.68 | 15.51 | 15.71 | 16.67 | 18.04 | 17.47 | 17.27 | 16.98 | 16.55 |
| 7 | 17.76 | 18.24 | 18.69 | 19.07 | 19.24 | 19.20 | 19.02 | 19.18 | 20.31 | 21.97 | 21.21 | 20.92 | 20.49 | 19.81 |
| 8 | 20.20 | 20.93 | 21.61 | 22.22 | 22.58 | 22.74 | 22.64 | 22.76 | 24.09 | 26.04 | 25.15 | 24.78 | 24.23 | 23.32 |
| 9 | 22.41 | 23.42 | 24.35 | 25.07 | 25.58 | 25.81 | 25.82 | 26.09 | 27.66 | 29.94 | 29.10 | 28.71 | 28.10 | 26.97 |
| 10 | 24.46 | 25.80 | 26.88 | 27.94 | 28.59 | 28.95 | 29.01 | 29.32 | 31.07 | 33.62 | 32.68 | 32.23 | 31.56 | 30.41 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 32.675 |
| SC2 | 0 | 8 | 22.762 |
| SC3 | -18 | 7 | 19.163 |
| SC4 | -25 | 6 | 15.461 |
| SC5 | -34 | 6 | 15.109 |
| A | 2567 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2567 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.