EA-363EC10-C11 C
33.87 kW
Defrost: None
Product code: EA-445AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 19,041 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 100.1 m² |
| Inner volume | 34.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 168 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-445AE7-C01 C | None |
|---|---|
| EA-445AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.52 | 12.69 | 12.85 | 12.98 | 12.99 | 12.91 | 12.76 | 13.07 | 13.92 | 15.03 | 14.64 | 14.49 | 14.28 | 13.97 |
| 5 | 16.36 | 16.86 | 17.25 | 17.64 | 17.81 | 17.82 | 17.67 | 18.00 | 19.13 | 20.71 | 20.13 | 19.94 | 19.68 | 19.32 |
| 6 | 19.84 | 20.76 | 21.59 | 22.33 | 22.79 | 22.96 | 22.87 | 23.21 | 24.64 | 26.65 | 25.88 | 25.59 | 25.16 | 24.48 |
| 7 | 22.78 | 24.09 | 25.29 | 26.21 | 26.93 | 27.36 | 27.55 | 28.01 | 29.79 | 32.39 | 31.64 | 31.32 | 30.87 | 30.11 |
| 8 | 25.46 | 26.98 | 28.64 | 30.06 | 31.07 | 31.71 | 32.03 | 32.56 | 34.62 | 37.65 | 36.79 | 36.42 | 35.86 | 34.90 |
| 9 | 27.89 | 29.92 | 31.97 | 33.81 | 35.14 | 35.99 | 36.48 | 37.14 | 39.49 | 42.95 | 42.02 | 41.59 | 40.93 | 39.77 |
| 10 | ≈ 29.91 | 32.59 | 35.12 | 37.40 | 39.06 | 40.23 | 40.90 | 41.71 | 44.38 | 48.27 | 47.29 | 46.81 | 46.06 | 44.73 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 47.292 |
| SC2 | 0 | 8 | 32.561 |
| SC3 | -18 | 7 | 26.531 |
| SC4 | -25 | 6 | 21.587 |
| SC5 | -34 | 6 | 20.063 |
| A | 3167 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.