EA-250BE10-C10 C
22.19 kW
Defrost: None
Product code: EA-535AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,571 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 82.2 m² |
| Inner volume | 24.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 124 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-535AE6-C01 C | None |
|---|---|
| EA-535AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.51 | 8.51 | 8.54 | 8.59 | 8.58 | 8.53 | 8.44 | 8.67 | 9.25 | 10.03 | 9.85 | 9.77 | 9.66 | 9.49 |
| 5 | 11.09 | 11.25 | 11.41 | 11.55 | 11.60 | 11.56 | 11.44 | 11.65 | 12.38 | 13.42 | 13.06 | 12.94 | 12.78 | 12.57 |
| 6 | 13.65 | 14.01 | 14.34 | 14.60 | 14.75 | 14.76 | 14.65 | 14.83 | 15.73 | 17.03 | 16.51 | 16.32 | 16.03 | 15.59 |
| 7 | 16.00 | 16.60 | 17.17 | 17.68 | 17.96 | 18.05 | 17.97 | 18.15 | 19.24 | 20.84 | 20.19 | 19.93 | 19.54 | 18.90 |
| 8 | 18.04 | 18.88 | 19.67 | 20.37 | 20.75 | 21.02 | 21.08 | 21.36 | 22.68 | 24.62 | 23.95 | 23.64 | 23.16 | 22.36 |
| 9 | 19.92 | 21.05 | 21.98 | 22.90 | 23.50 | 23.87 | 24.02 | 24.34 | 25.84 | 28.03 | 27.33 | 27.01 | 26.53 | 25.67 |
| 10 | 21.65 | 22.97 | 24.28 | 25.44 | 26.23 | 26.73 | 26.96 | 27.34 | 29.02 | 31.48 | 30.71 | 30.35 | 29.79 | 28.78 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.713 |
| SC2 | 0 | 8 | 21.362 |
| SC3 | -18 | 7 | 17.817 |
| SC4 | -25 | 6 | 14.339 |
| SC5 | -34 | 6 | 13.745 |
| A | 2857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.