Skip to Content

Unit cooler EA-630BE10-C05 C

Unit cooler EA-630BE10-C05 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-630BE10-C05 C

Cooling capacity i
11.25 kW
Air flow
5,961 m³/h
Fin spacing
10.0 mm
Air throw
7 m
Fans
6 × ⌀300 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 6 — Number of fans (one digit).
  • C
    Fan diameter: 30 — Ø300 mm
  • D
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 05 — Ø300: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 5,961 m³/h
Air throw 7 m
External surface 38.4 m²
Inner volume 17.4 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 72 kg
Fans
Quantity 6
Diameter 300 mm
Speed 1,300 rpm
Power 720 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 48.0 dB(A)
Sound power 70.0 dB(A)
Energy class D
Connections
Inlet Ø15,9
Outlet Ø28
Defrost
EA-630BE10-C05 C None
EA-630BE10-C05 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
10.849 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 4.22 4.29 4.37 4.44 4.47 4.47 4.43 4.57 4.88 5.31 5.21 5.18 5.14 5.07
5 5.39 5.57 5.74 5.89 5.97 6.00 5.97 6.10 6.49 7.05 6.87 6.80 6.71 6.57
6 6.53 6.83 7.11 7.33 7.49 7.56 7.56 7.69 8.17 8.87 8.62 8.52 8.37 8.13
7 7.55 7.99 8.41 8.77 9.01 9.14 9.16 9.32 9.90 10.73 10.44 10.31 10.12 9.82
8 8.46 9.03 9.57 10.04 10.33 10.54 10.65 10.85 11.54 12.55 12.26 12.13 11.92 11.55
9 9.26 9.99 10.58 11.20 11.63 11.92 12.08 12.32 13.10 14.24 13.94 13.79 13.57 13.18
10 ≈ 9.99 10.88 11.63 12.35 12.90 13.28 13.49 13.78 14.66 15.94 15.62 15.46 15.21 14.77

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 15.619
SC2 0 8 10.849
SC3 -18 7 8.879
SC4 -25 6 7.109
SC5 -34 6 6.602

Dimensions

Dimension drawing of EA-630BE10-C05 C
Dimension drawing
Dimensions as drawn
A 2557 mm
B 567 mm
C 445 mm
F 395 mm
E1 385 mm
E2 367 mm
E 2235 mm
D IN 1 x Ø15,9
D OUT 1 x Ø28
Overall [mm]
Length 2407 mm
Width 567 mm
Height 445 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.