ED-230AC7-C21 C
4.38 kW
Defrost: None
Product code: ED-135AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,384 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 17.2 m² |
| Inner volume | 6.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-135AE7-C21 C | None |
|---|---|
| ED-135AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.76 | 1.72 | 1.70 | 1.70 | 1.69 | 1.68 | 1.66 | 1.70 | 1.80 | 1.95 | 1.91 | 1.90 | 1.88 | 1.85 |
| 5 | 2.36 | 2.32 | 2.31 | 2.30 | 2.29 | 2.27 | 2.24 | 2.27 | 2.41 | 2.61 | 2.55 | 2.53 | 2.50 | 2.46 |
| 6 | 2.97 | 2.95 | 2.95 | 2.95 | 2.94 | 2.91 | 2.88 | 2.90 | 3.07 | 3.32 | 3.22 | 3.19 | 3.14 | 3.07 |
| 7 | 3.57 | 3.58 | 3.60 | 3.63 | 3.63 | 3.60 | 3.56 | 3.58 | 3.79 | 4.09 | 3.95 | 3.90 | 3.83 | 3.72 |
| 8 | 4.17 | 4.21 | 4.27 | 4.32 | 4.34 | 4.32 | 4.28 | 4.29 | 4.54 | 4.90 | 4.73 | 4.66 | 4.56 | 4.41 |
| 9 | 4.74 | 4.84 | 4.93 | 5.02 | 5.06 | 5.05 | 5.02 | 5.03 | 5.32 | 5.73 | 5.54 | 5.46 | 5.34 | 5.14 |
| 10 | 5.28 | 5.43 | 5.58 | 5.71 | 5.78 | 5.79 | 5.76 | 5.78 | 6.12 | 6.60 | 6.38 | 6.29 | 6.15 | 5.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.382 |
| SC2 | 0 | 8 | 4.289 |
| SC3 | -18 | 7 | 3.631 |
| SC4 | -25 | 6 | 2.945 |
| SC5 | -34 | 6 | 2.964 |
| A | 948 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.