EG-125AC4-C23 C
1.27 kW
Defrost: None
Product code: EG-130AB7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,239 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 3.7 m² |
| Inner volume | 1.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 20 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 62.0 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø12,7 |
| EG-130AB7-C25 C | None |
|---|---|
| EG-130AB7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.46 | 0.45 | 0.44 | 0.43 | 0.43 | 0.42 | 0.42 | 0.42 | 0.45 | 0.48 | 0.47 | 0.47 | 0.46 | 0.45 |
| 5 | 0.64 | 0.62 | 0.61 | 0.61 | 0.60 | 0.59 | 0.58 | 0.59 | 0.62 | 0.67 | 0.65 | 0.65 | 0.64 | 0.62 |
| 6 | 0.82 | 0.81 | 0.81 | 0.80 | 0.80 | 0.79 | 0.77 | 0.78 | 0.82 | 0.88 | 0.86 | 0.85 | 0.83 | 0.81 |
| 7 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 0.98 | 0.99 | 1.04 | 1.12 | 1.08 | 1.07 | 1.05 | 1.02 |
| 8 | 1.19 | 1.20 | 1.21 | 1.23 | 1.23 | 1.22 | 1.21 | 1.21 | 1.28 | 1.38 | 1.33 | 1.31 | 1.28 | 1.24 |
| 9 | 1.35 | 1.37 | 1.40 | 1.43 | 1.44 | 1.45 | 1.44 | 1.45 | 1.53 | 1.65 | 1.59 | 1.57 | 1.54 | 1.49 |
| 10 | 1.50 | 1.53 | 1.57 | 1.61 | 1.63 | 1.64 | 1.65 | 1.66 | 1.76 | 1.91 | 1.86 | 1.84 | 1.81 | 1.74 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 1.861 |
| SC2 | 0 | 8 | 1.210 |
| SC3 | -18 | 7 | 1.012 |
| SC4 | -25 | 6 | 0.807 |
| SC5 | -34 | 6 | 0.821 |
| A | 1146 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E | 835 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø12,7 |
| Length | 1146 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.