EG-130AE4-C25 C
2.39 kW
Defrost: None
Product code: EG-225BC7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,425 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 7.4 m² |
| Inner volume | 1.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 25 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.4 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EG-225BC7-C23 C | None |
|---|---|
| EG-225BC7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.89 | 0.89 | 0.88 | 0.89 | 0.88 | 0.88 | 0.87 | 0.89 | 0.94 | 1.02 | 1.00 | 0.99 | 0.98 | 0.97 |
| 5 | 1.18 | 1.19 | 1.20 | 1.21 | 1.21 | 1.20 | 1.18 | 1.20 | 1.28 | 1.38 | 1.34 | 1.33 | 1.32 | 1.29 |
| 6 | 1.47 | 1.49 | 1.52 | 1.54 | 1.55 | 1.54 | 1.53 | 1.55 | 1.64 | 1.77 | 1.72 | 1.70 | 1.67 | 1.62 |
| 7 | 1.74 | 1.79 | 1.83 | 1.87 | 1.90 | 1.90 | 1.89 | 1.91 | 2.02 | 2.19 | 2.12 | 2.09 | 2.05 | 1.98 |
| 8 | 1.98 | 2.05 | 2.12 | 2.18 | 2.23 | 2.25 | 2.25 | 2.28 | 2.42 | 2.61 | 2.53 | 2.50 | 2.44 | 2.36 |
| 9 | 2.21 | 2.30 | 2.40 | 2.48 | 2.53 | 2.56 | 2.57 | 2.61 | 2.77 | 3.00 | 2.92 | 2.89 | 2.83 | 2.74 |
| 10 | 2.44 | 2.56 | 2.67 | 2.77 | 2.84 | 2.88 | 2.90 | 2.94 | 3.12 | 3.38 | 3.29 | 3.25 | 3.19 | 3.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.292 |
| SC2 | 0 | 8 | 2.280 |
| SC3 | -18 | 7 | 1.885 |
| SC4 | -25 | 6 | 1.515 |
| SC5 | -34 | 6 | 1.474 |
| A | 1066 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 378 mm |
| E | 755 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1066 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.