EG-230BE7-C21 C
4.59 kW
Defrost: None
Product code: EG-230AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,316 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 14.9 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 68.3 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-230AE7-C21 C | None |
|---|---|
| EG-230AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.77 | 1.76 | 1.75 | 1.76 | 1.75 | 1.74 | 1.72 | 1.76 | 1.87 | 2.03 | 1.99 | 1.98 | 1.96 | 1.92 |
| 5 | 2.34 | 2.34 | 2.35 | 2.37 | 2.37 | 2.36 | 2.33 | 2.37 | 2.51 | 2.72 | 2.65 | 2.62 | 2.59 | 2.54 |
| 6 | 2.89 | 2.92 | 2.96 | 3.01 | 3.02 | 3.01 | 2.99 | 3.02 | 3.20 | 3.46 | 3.35 | 3.31 | 3.26 | 3.16 |
| 7 | 3.42 | 3.50 | 3.57 | 3.65 | 3.69 | 3.69 | 3.67 | 3.70 | 3.92 | 4.24 | 4.11 | 4.05 | 3.97 | 3.84 |
| 8 | 3.90 | 4.02 | 4.14 | 4.25 | 4.33 | 4.36 | 4.37 | 4.40 | 4.66 | 5.04 | 4.89 | 4.83 | 4.73 | 4.56 |
| 9 | 4.34 | 4.51 | 4.67 | 4.82 | 4.92 | 4.97 | 4.99 | 5.05 | 5.36 | 5.80 | 5.66 | 5.59 | 5.49 | 5.29 |
| 10 | 4.80 | 5.01 | 5.21 | 5.39 | 5.51 | 5.58 | 5.61 | 5.68 | 6.02 | 6.53 | 6.37 | 6.29 | 6.18 | 5.96 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.368 |
| SC2 | 0 | 8 | 4.400 |
| SC3 | -18 | 7 | 3.666 |
| SC4 | -25 | 6 | 2.963 |
| SC5 | -34 | 6 | 2.898 |
| A | 1946 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1946 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.