EG-330AB7-C25 C
4.08 kW
Defrost: None
Product code: EG-230AE7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,975 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 14.9 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-230AE7-C25 C | None |
|---|---|
| EG-230AE7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.62 | 1.60 | 1.60 | 1.60 | 1.60 | 1.59 | 1.57 | 1.62 | 1.73 | 1.88 | 1.84 | 1.83 | 1.82 | 1.80 |
| 5 | 2.13 | 2.13 | 2.13 | 2.15 | 2.15 | 2.13 | 2.11 | 2.15 | 2.29 | 2.48 | 2.41 | 2.39 | 2.36 | 2.32 |
| 6 | 2.63 | 2.65 | 2.68 | 2.71 | 2.72 | 2.71 | 2.68 | 2.72 | 2.88 | 3.12 | 3.02 | 2.98 | 2.93 | 2.84 |
| 7 | 3.12 | 3.17 | 3.23 | 3.29 | 3.31 | 3.31 | 3.28 | 3.31 | 3.51 | 3.79 | 3.66 | 3.61 | 3.54 | 3.42 |
| 8 | 3.59 | 3.68 | 3.78 | 3.86 | 3.91 | 3.92 | 3.89 | 3.92 | 4.15 | 4.49 | 4.34 | 4.28 | 4.19 | 4.04 |
| 9 | 4.01 | 4.14 | 4.27 | 4.39 | 4.46 | 4.50 | 4.50 | 4.55 | 4.81 | 5.20 | 5.04 | 4.96 | 4.86 | 4.68 |
| 10 | 4.43 | 4.58 | 4.75 | 4.90 | 5.00 | 5.05 | 5.06 | 5.12 | 5.42 | 5.87 | 5.71 | 5.64 | 5.53 | 5.33 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.710 |
| SC2 | 0 | 8 | 3.924 |
| SC3 | -18 | 7 | 3.302 |
| SC4 | -25 | 6 | 2.683 |
| SC5 | -34 | 6 | 2.640 |
| A | 1946 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1946 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.