EG-425BC7-C23 C
4.72 kW
Defrost: None
Product code: EG-325AE4-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,687 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 26.6 m² |
| Inner volume | 4.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 40 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.4 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-325AE4-C23 C | None |
|---|---|
| EG-325AE4-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.96 | 1.97 | 1.99 | 2.01 | 2.02 | 2.03 | 2.02 | 2.07 | 2.20 | 2.40 | 2.35 | 2.34 | 2.32 | 2.29 |
| 5 | 2.48 | 2.52 | 2.56 | 2.60 | 2.63 | 2.63 | 2.62 | 2.66 | 2.83 | 3.07 | 2.99 | 2.97 | 2.92 | 2.85 |
| 6 | 2.99 | 3.06 | 3.13 | 3.20 | 3.24 | 3.25 | 3.25 | 3.28 | 3.48 | 3.78 | 3.67 | 3.63 | 3.56 | 3.46 |
| 7 | 3.48 | 3.59 | 3.70 | 3.80 | 3.86 | 3.88 | 3.88 | 3.92 | 4.15 | 4.50 | 4.37 | 4.32 | 4.23 | 4.09 |
| 8 | 3.92 | 4.07 | 4.22 | 4.36 | 4.45 | 4.50 | 4.51 | 4.56 | 4.83 | 5.23 | 5.08 | 5.02 | 4.92 | 4.74 |
| 9 | 4.33 | 4.54 | 4.73 | 4.91 | 5.02 | 5.09 | 5.11 | 5.16 | 5.47 | 5.93 | 5.78 | 5.71 | 5.60 | 5.40 |
| 10 | 4.75 | 5.01 | 5.24 | 5.46 | 5.58 | 5.67 | 5.71 | 5.77 | 6.12 | 6.62 | 6.46 | 6.38 | 6.25 | 6.03 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.456 |
| SC2 | 0 | 8 | 4.558 |
| SC3 | -18 | 7 | 3.825 |
| SC4 | -25 | 6 | 3.132 |
| SC5 | -34 | 6 | 3.010 |
| A | 2146 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 618 mm |
| E2 | 600 mm |
| E | 1835 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 2146 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.