EG-330BC4-C21 C
6.60 kW
Defrost: None
Product code: EG-330AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,638 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 23.6 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 49 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.8 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-330AC4-C21 C | None |
|---|---|
| EG-330AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.55 | 2.56 | 2.59 | 2.62 | 2.62 | 2.62 | 2.60 | 2.66 | 2.83 | 3.07 | 3.01 | 2.99 | 2.96 | 2.91 |
| 5 | 3.31 | 3.39 | 3.46 | 3.53 | 3.56 | 3.56 | 3.54 | 3.60 | 3.83 | 4.15 | 4.05 | 4.01 | 3.96 | 3.89 |
| 6 | 3.99 | 4.13 | 4.26 | 4.39 | 4.47 | 4.51 | 4.53 | 4.60 | 4.90 | 5.31 | 5.17 | 5.12 | 5.04 | 4.92 |
| 7 | 4.65 | 4.84 | 5.01 | 5.18 | 5.30 | 5.37 | 5.40 | 5.48 | 5.82 | 6.33 | 6.19 | 6.13 | 6.05 | 5.91 |
| 8 | 5.23 | 5.50 | 5.76 | 5.99 | 6.15 | 6.24 | 6.28 | 6.37 | 6.77 | 7.36 | 7.19 | 7.12 | 7.01 | 6.83 |
| 9 | 5.77 | 6.13 | 6.47 | 6.77 | 6.98 | 7.11 | 7.18 | 7.26 | 7.72 | 8.38 | 8.20 | 8.11 | 7.99 | 7.77 |
| 10 | 6.26 | 6.72 | 7.15 | 7.53 | 7.75 | 7.93 | 8.04 | 8.16 | 8.68 | 9.43 | 9.23 | 9.13 | 8.98 | 8.73 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.229 |
| SC2 | 0 | 8 | 6.370 |
| SC3 | -18 | 7 | 5.237 |
| SC4 | -25 | 6 | 4.263 |
| SC5 | -34 | 6 | 4.028 |
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |