EG-330BC4-C25 C
6.06 kW
Defrost: None
Product code: EG-330AC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,141 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 23.6 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-330AC4-C25 C | None |
|---|---|
| EG-330AC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.39 | 2.40 | 2.42 | 2.44 | 2.45 | 2.44 | 2.42 | 2.50 | 2.67 | 2.90 | 2.85 | 2.84 | 2.81 | 2.77 |
| 5 | 3.10 | 3.16 | 3.22 | 3.27 | 3.30 | 3.29 | 3.27 | 3.34 | 3.55 | 3.85 | 3.76 | 3.72 | 3.68 | 3.62 |
| 6 | 3.77 | 3.88 | 4.00 | 4.10 | 4.17 | 4.19 | 4.17 | 4.24 | 4.50 | 4.88 | 4.74 | 4.69 | 4.61 | 4.49 |
| 7 | 4.36 | 4.53 | 4.70 | 4.85 | 4.94 | 4.99 | 5.00 | 5.08 | 5.40 | 5.87 | 5.72 | 5.66 | 5.57 | 5.43 |
| 8 | 4.94 | 5.18 | 5.40 | 5.60 | 5.72 | 5.79 | 5.81 | 5.89 | 6.26 | 6.80 | 6.63 | 6.55 | 6.44 | 6.25 |
| 9 | 5.46 | 5.78 | 6.07 | 6.33 | 6.49 | 6.59 | 6.62 | 6.72 | 7.13 | 7.74 | 7.55 | 7.46 | 7.32 | 7.09 |
| 10 | 5.94 | 6.35 | 6.71 | 7.03 | 7.26 | 7.39 | 7.43 | 7.54 | 8.00 | 8.68 | 8.47 | 8.37 | 8.21 | 7.95 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.467 |
| SC2 | 0 | 8 | 5.894 |
| SC3 | -18 | 7 | 4.889 |
| SC4 | -25 | 6 | 3.995 |
| SC5 | -34 | 6 | 3.796 |
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.