EG-235BC7-C21 C
5.58 kW
Defrost: None
Product code: EG-330AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,876 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 14.9 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 49 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.1 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-330AC7-C21 C | None |
|---|---|
| EG-330AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.11 | 2.10 | 2.10 | 2.10 | 2.10 | 2.08 | 2.06 | 2.10 | 2.23 | 2.41 | 2.35 | 2.32 | 2.29 | 2.25 |
| 5 | 2.80 | 2.82 | 2.85 | 2.89 | 2.89 | 2.88 | 2.86 | 2.89 | 3.07 | 3.32 | 3.23 | 3.20 | 3.16 | 3.10 |
| 6 | 3.46 | 3.54 | 3.62 | 3.69 | 3.73 | 3.73 | 3.72 | 3.75 | 3.98 | 4.30 | 4.18 | 4.13 | 4.06 | 3.96 |
| 7 | 4.05 | 4.17 | 4.30 | 4.43 | 4.51 | 4.56 | 4.58 | 4.64 | 4.93 | 5.35 | 5.20 | 5.14 | 5.06 | 4.92 |
| 8 | 4.62 | 4.80 | 4.95 | 5.12 | 5.24 | 5.31 | 5.34 | 5.41 | 5.75 | 6.25 | 6.11 | 6.05 | 5.97 | 5.82 |
| 9 | 5.13 | 5.38 | 5.61 | 5.82 | 5.97 | 6.06 | 6.11 | 6.19 | 6.58 | 7.15 | 7.00 | 6.93 | 6.83 | 6.66 |
| 10 | 5.60 | 5.93 | 6.23 | 6.49 | 6.69 | 6.82 | 6.89 | 6.98 | 7.42 | 8.06 | 7.89 | 7.82 | 7.70 | 7.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.890 |
| SC2 | 0 | 8 | 5.409 |
| SC3 | -18 | 7 | 4.462 |
| SC4 | -25 | 6 | 3.618 |
| SC5 | -34 | 6 | 3.482 |
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.