EA-230AC4-C05 C
4.25 kW
Defrost: None
Product code: EA-135AG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,088 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 14.0 m² |
| Inner volume | 6.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 41 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-135AG10-C01 C | None |
|---|---|
| EA-135AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.62 | 1.62 | 1.62 | 1.63 | 1.63 | 1.61 | 1.59 | 1.64 | 1.74 | 1.89 | 1.85 | 1.84 | 1.82 | 1.78 |
| 5 | 2.12 | 2.14 | 2.17 | 2.19 | 2.20 | 2.19 | 2.17 | 2.20 | 2.34 | 2.53 | 2.46 | 2.44 | 2.41 | 2.36 |
| 6 | 2.59 | 2.66 | 2.72 | 2.77 | 2.80 | 2.79 | 2.77 | 2.80 | 2.97 | 3.22 | 3.12 | 3.08 | 3.02 | 2.94 |
| 7 | 3.04 | 3.15 | 3.26 | 3.35 | 3.40 | 3.41 | 3.40 | 3.43 | 3.64 | 3.93 | 3.81 | 3.75 | 3.68 | 3.55 |
| 8 | 3.49 | 3.65 | 3.80 | 3.93 | 4.01 | 4.03 | 4.03 | 4.07 | 4.31 | 4.67 | 4.52 | 4.46 | 4.36 | 4.20 |
| 9 | 3.88 | 4.10 | 4.30 | 4.48 | 4.60 | 4.66 | 4.67 | 4.72 | 5.00 | 5.41 | 5.25 | 5.18 | 5.06 | 4.86 |
| 10 | 4.23 | 4.51 | 4.76 | 4.98 | 5.14 | 5.21 | 5.26 | 5.33 | 5.66 | 6.14 | 5.98 | 5.90 | 5.77 | 5.54 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.979 |
| SC2 | 0 | 8 | 4.070 |
| SC3 | -18 | 7 | 3.372 |
| SC4 | -25 | 6 | 2.717 |
| SC5 | -34 | 6 | 2.609 |
| A | 857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.