EA-163FD10-C13 C
16.11 kW
Defrost: None
Product code: EA-163GD10-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,505 m³/h |
|---|---|
| Air throw | 29 m |
| External surface | 66.0 m² |
| Inner volume | 26.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 145 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 1,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.7 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163GD10-C19 C | None |
|---|---|
| EA-163GD10-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.32 | 6.22 | 6.17 | 6.15 | 6.12 | 6.07 | 6.03 | 6.03 | 6.38 | 6.89 | 6.72 | 6.66 | 6.57 | 6.44 |
| 5 | 8.34 | 8.29 | 8.28 | 8.30 | 8.28 | 8.23 | 8.17 | 8.16 | 8.63 | 9.32 | 9.06 | 8.97 | 8.84 | 8.64 |
| 6 | 10.38 | 10.42 | 10.49 | 10.56 | 10.58 | 10.55 | 10.49 | 10.47 | 11.08 | 11.95 | 11.62 | 11.49 | 11.31 | 11.03 |
| 7 | 12.31 | 12.50 | 12.70 | 12.88 | 12.97 | 12.98 | 12.93 | 12.91 | 13.66 | 14.76 | 14.34 | 14.18 | 13.95 | 13.58 |
| 8 | 14.13 | 14.52 | 14.87 | 15.14 | 15.32 | 15.41 | 15.41 | 15.43 | 16.33 | 17.66 | 17.18 | 16.99 | 16.71 | 16.27 |
| 9 | 15.85 | 16.37 | 16.91 | 17.39 | 17.70 | 17.87 | 17.94 | 17.99 | 19.06 | 20.63 | 20.11 | 19.90 | 19.58 | 19.07 |
| 10 | 17.30 | 18.07 | 18.78 | 19.44 | 19.89 | 20.20 | 20.40 | 20.57 | 21.82 | 23.64 | 23.08 | 22.85 | 22.51 | 21.93 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.70 | 5.60 | 5.55 | 5.54 | 5.51 | 5.48 | 5.44 | 5.48 | 5.80 | 6.27 | 6.13 | 6.07 | 6.00 | 5.88 |
| 5 | 7.50 | 7.43 | 7.41 | 7.42 | 7.40 | 7.35 | 7.29 | 7.32 | 7.76 | 8.39 | 8.17 | 8.09 | 7.99 | 7.82 |
| 6 | 9.33 | 9.30 | 9.34 | 9.40 | 9.40 | 9.36 | 9.29 | 9.31 | 9.86 | 10.65 | 10.36 | 10.25 | 10.09 | 9.85 |
| 7 | 11.09 | 11.19 | 11.31 | 11.44 | 11.47 | 11.45 | 11.39 | 11.40 | 12.07 | 13.04 | 12.66 | 12.52 | 12.31 | 11.98 |
| 8 | 12.78 | 13.02 | 13.26 | 13.48 | 13.59 | 13.61 | 13.56 | 13.58 | 14.37 | 15.53 | 15.08 | 14.89 | 14.63 | 14.22 |
| 9 | 14.38 | 14.79 | 15.17 | 15.46 | 15.66 | 15.75 | 15.74 | 15.78 | 16.71 | 18.06 | 17.56 | 17.35 | 17.05 | 16.56 |
| 10 | 15.88 | 16.42 | 16.96 | 17.44 | 17.74 | 17.90 | 17.94 | 18.02 | 19.09 | 20.65 | 20.11 | 19.88 | 19.53 | 18.97 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 23.083 | 20.106 |
| SC2 | 0 | 8 | 15.425 | 13.575 |
| SC3 | -18 | 7 | 12.926 | 11.462 |
| SC4 | -25 | 6 | 10.493 | 9.338 |
| SC5 | -34 | 6 | 10.399 | 9.342 |
| A | 1715 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E | 1335 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1715 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.