EA-230AE6-C01 C
5.20 kW
Defrost: None
Product code: EA-230BC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,641 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 25.2 m² |
| Inner volume | 4.8 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230BC4-C01 C | None |
|---|---|
| EA-230BC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.96 | 1.94 | 1.94 | 1.94 | 1.94 | 1.93 | 1.92 | 1.96 | 2.08 | 2.26 | 2.22 | 2.20 | 2.18 | 2.15 |
| 5 | 2.59 | 2.59 | 2.61 | 2.63 | 2.63 | 2.61 | 2.59 | 2.62 | 2.79 | 3.02 | 2.94 | 2.92 | 2.89 | 2.84 |
| 6 | 3.23 | 3.27 | 3.31 | 3.36 | 3.37 | 3.36 | 3.34 | 3.36 | 3.56 | 3.85 | 3.74 | 3.70 | 3.65 | 3.56 |
| 7 | 3.83 | 3.93 | 4.03 | 4.11 | 4.15 | 4.15 | 4.13 | 4.15 | 4.40 | 4.76 | 4.61 | 4.55 | 4.47 | 4.35 |
| 8 | 4.36 | 4.52 | 4.67 | 4.81 | 4.89 | 4.94 | 4.94 | 4.98 | 5.27 | 5.70 | 5.53 | 5.46 | 5.36 | 5.20 |
| 9 | 4.84 | 5.07 | 5.27 | 5.43 | 5.55 | 5.62 | 5.65 | 5.71 | 6.06 | 6.57 | 6.41 | 6.35 | 6.25 | 6.08 |
| 10 | 5.29 | 5.55 | 5.82 | 6.06 | 6.22 | 6.31 | 6.36 | 6.43 | 6.82 | 7.40 | 7.23 | 7.15 | 7.04 | 6.84 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.226 |
| SC2 | 0 | 8 | 4.976 |
| SC3 | -18 | 7 | 4.133 |
| SC4 | -25 | 6 | 3.310 |
| SC5 | -34 | 6 | 3.240 |
| A | 1357 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.