EA-240AE4-C01 C
11.94 kW
Defrost: None
Product code: EA-240AG7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,141 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 49.0 m² |
| Inner volume | 16.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 85 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-240AG7-C01 C | None |
|---|---|
| EA-240AG7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.69 | 4.67 | 4.68 | 4.70 | 4.68 | 4.65 | 4.60 | 4.74 | 5.06 | 5.49 | 5.39 | 5.36 | 5.33 | 5.24 |
| 5 | 6.11 | 6.15 | 6.22 | 6.28 | 6.28 | 6.25 | 6.17 | 6.29 | 6.69 | 7.25 | 7.05 | 6.98 | 6.89 | 6.77 |
| 6 | 7.49 | 7.63 | 7.77 | 7.90 | 7.95 | 7.93 | 7.85 | 7.94 | 8.42 | 9.11 | 8.81 | 8.70 | 8.54 | 8.29 |
| 7 | 8.85 | 9.11 | 9.35 | 9.54 | 9.65 | 9.66 | 9.58 | 9.67 | 10.24 | 11.07 | 10.68 | 10.53 | 10.30 | 9.92 |
| 8 | 10.09 | 10.49 | 10.87 | 11.19 | 11.37 | 11.40 | 11.34 | 11.44 | 12.10 | 13.08 | 12.64 | 12.45 | 12.16 | 11.68 |
| 9 | 11.22 | 11.76 | 12.26 | 12.70 | 12.97 | 13.11 | 13.13 | 13.21 | 13.98 | 15.10 | 14.62 | 14.40 | 14.06 | 13.48 |
| 10 | 12.23 | 12.93 | 13.57 | 14.14 | 14.44 | 14.65 | 14.70 | 14.87 | 15.77 | 17.06 | 16.59 | 16.36 | 15.99 | 15.31 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.594 |
| SC2 | 0 | 8 | 11.435 |
| SC3 | -18 | 7 | 9.595 |
| SC4 | -25 | 6 | 7.774 |
| SC5 | -34 | 6 | 7.526 |
| A | 1467 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.