EA-145AC8-C01 C
5.83 kW
Defrost: None
Product code: EA-330AC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,541 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 20.7 m² |
| Inner volume | 7.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AC7-C05 C | None |
|---|---|
| EA-330AC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.21 | 2.18 | 2.16 | 2.16 | 2.15 | 2.13 | 2.11 | 2.16 | 2.30 | 2.48 | 2.43 | 2.41 | 2.38 | 2.34 |
| 5 | 2.94 | 2.93 | 2.93 | 2.94 | 2.93 | 2.91 | 2.88 | 2.92 | 3.10 | 3.36 | 3.28 | 3.25 | 3.21 | 3.16 |
| 6 | 3.67 | 3.69 | 3.73 | 3.77 | 3.77 | 3.76 | 3.72 | 3.76 | 3.98 | 4.31 | 4.18 | 4.14 | 4.07 | 3.98 |
| 7 | 4.39 | 4.47 | 4.53 | 4.61 | 4.64 | 4.64 | 4.61 | 4.64 | 4.92 | 5.32 | 5.15 | 5.09 | 5.00 | 4.85 |
| 8 | 5.07 | 5.21 | 5.35 | 5.47 | 5.54 | 5.55 | 5.53 | 5.57 | 5.90 | 6.38 | 6.18 | 6.10 | 5.99 | 5.80 |
| 9 | 5.69 | 5.89 | 6.09 | 6.27 | 6.39 | 6.46 | 6.47 | 6.52 | 6.89 | 7.46 | 7.24 | 7.15 | 7.01 | 6.78 |
| 10 | 6.24 | 6.52 | 6.78 | 7.01 | 7.14 | 7.24 | 7.29 | 7.38 | 7.83 | 8.49 | 8.30 | 8.21 | 8.06 | 7.79 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.298 |
| SC2 | 0 | 8 | 5.566 |
| SC3 | -18 | 7 | 4.629 |
| SC4 | -25 | 6 | 3.727 |
| SC5 | -34 | 6 | 3.676 |
| A | 1657 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 450.5 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.