EA-445AG8-C01 C
36.66 kW
Defrost: None
Product code: EA-363EE7-C06 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 24,715 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 202.8 m² |
| Inner volume | 60.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 294 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 78.3 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363EE7-C06 C | None |
|---|---|
| EA-363EE7-C06 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.39 | 14.23 | 14.17 | 14.18 | 14.15 | 14.08 | 13.99 | 14.26 | 15.12 | 16.38 | 16.04 | 15.92 | 15.75 | 15.49 |
| 5 | 18.89 | 18.87 | 18.91 | 19.00 | 18.98 | 18.88 | 18.73 | 18.97 | 20.14 | 21.80 | 21.30 | 21.12 | 20.88 | 20.52 |
| 6 | 23.46 | 23.67 | 23.90 | 24.13 | 24.16 | 24.07 | 23.88 | 24.08 | 25.53 | 27.61 | 26.86 | 26.60 | 26.22 | 25.65 |
| 7 | 27.80 | 28.37 | 28.90 | 29.37 | 29.56 | 29.54 | 29.35 | 29.51 | 31.23 | 33.76 | 32.78 | 32.41 | 31.87 | 31.04 |
| 8 | 31.89 | 32.92 | 33.69 | 34.49 | 34.92 | 35.05 | 34.93 | 35.12 | 37.20 | 40.22 | 39.02 | 38.54 | 37.85 | 36.75 |
| 9 | 35.46 | 36.94 | 38.26 | 39.47 | 40.25 | 40.65 | 40.65 | 40.88 | 43.32 | 46.87 | 45.50 | 44.95 | 44.13 | 42.78 |
| 10 | 38.79 | 40.70 | 42.45 | 44.01 | 45.04 | 45.64 | 45.93 | 46.39 | 49.24 | 53.41 | 52.12 | 51.49 | 50.55 | 48.97 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.56 | 12.39 | 12.34 | 12.37 | 12.35 | 12.29 | 12.20 | 12.54 | 13.35 | 14.48 | 14.21 | 14.10 | 13.96 | 13.75 |
| 5 | 16.42 | 16.32 | 16.33 | 16.39 | 16.36 | 16.26 | 16.09 | 16.44 | 17.49 | 18.97 | 18.55 | 18.40 | 18.20 | 17.90 |
| 6 | 20.38 | 20.41 | 20.48 | 20.63 | 20.64 | 20.52 | 20.29 | 20.60 | 21.87 | 23.67 | 23.03 | 22.80 | 22.48 | 21.99 |
| 7 | 24.20 | 24.47 | 24.76 | 25.05 | 25.12 | 25.00 | 24.72 | 24.98 | 26.47 | 28.63 | 27.72 | 27.38 | 26.85 | 26.09 |
| 8 | 27.88 | 28.45 | 29.00 | 29.49 | 29.69 | 29.63 | 29.34 | 29.53 | 31.26 | 33.78 | 32.58 | 32.14 | 31.51 | 30.51 |
| 9 | 31.36 | 32.31 | 33.07 | 33.82 | 34.21 | 34.26 | 33.99 | 34.19 | 36.17 | 39.07 | 37.70 | 37.18 | 36.42 | 35.16 |
| 10 | 34.63 | 35.84 | 37.06 | 38.16 | 38.72 | 38.92 | 38.72 | 38.96 | 41.22 | 44.43 | 43.01 | 42.41 | 41.51 | 39.99 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 52.121 | 43.009 |
| SC2 | 0 | 8 | 35.115 | 29.531 |
| SC3 | -18 | 7 | 29.476 | 25.100 |
| SC4 | -25 | 6 | 23.901 | 20.482 |
| SC5 | -34 | 6 | 23.540 | 20.413 |
| A | 2815 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.