EA-280GE7-C01 C
51.71 kW
Defrost: None
Product code: EA-363FE10-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 46,004 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 183.1 m² |
| Inner volume | 78.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 387 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 5,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-363FE10-C08 C | None |
|---|---|
| EA-363FE10-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 19.60 | 19.22 | 18.98 | 18.84 | 18.64 | 18.42 | 18.19 | 18.27 | 19.31 | 20.82 | 20.25 | 20.05 | 19.76 | 19.33 |
| 5 | 26.34 | 26.06 | 25.98 | 25.94 | 25.76 | 25.48 | 25.14 | 25.21 | 26.69 | 28.77 | 27.93 | 27.64 | 27.18 | 26.49 |
| 6 | 32.92 | 33.12 | 33.33 | 33.53 | 33.46 | 33.19 | 32.81 | 32.83 | 34.73 | 37.42 | 36.24 | 35.81 | 35.21 | 34.30 |
| 7 | 39.24 | 39.99 | 40.67 | 41.25 | 41.43 | 41.24 | 40.92 | 40.94 | 43.28 | 46.66 | 45.18 | 44.62 | 43.81 | 42.54 |
| 8 | 45.16 | 46.38 | 47.65 | 48.73 | 49.30 | 49.46 | 49.29 | 49.38 | 52.25 | 56.40 | 54.66 | 53.98 | 52.97 | 51.37 |
| 9 | 50.12 | 52.10 | 53.93 | 55.59 | 56.67 | 57.31 | 57.61 | 57.98 | 61.41 | 66.40 | 64.47 | 63.69 | 62.54 | 60.62 |
| 10 | 54.81 | 57.49 | 59.94 | 62.11 | 63.57 | 64.48 | 64.95 | 65.51 | 69.54 | 75.43 | 73.72 | 73.00 | 71.92 | 70.05 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.32 | 16.95 | 16.75 | 16.64 | 16.50 | 16.33 | 16.16 | 16.35 | 17.30 | 18.69 | 18.23 | 18.06 | 17.83 | 17.48 |
| 5 | 23.10 | 22.84 | 22.71 | 22.66 | 22.50 | 22.27 | 21.99 | 22.15 | 23.48 | 25.35 | 24.67 | 24.44 | 24.11 | 23.61 |
| 6 | 29.01 | 28.96 | 29.00 | 29.05 | 28.96 | 28.72 | 28.38 | 28.49 | 30.16 | 32.53 | 31.54 | 31.19 | 30.70 | 29.95 |
| 7 | 34.67 | 35.00 | 35.35 | 35.69 | 35.73 | 35.52 | 35.18 | 35.25 | 37.29 | 40.21 | 38.93 | 38.45 | 37.75 | 36.67 |
| 8 | 40.08 | 40.90 | 41.66 | 42.33 | 42.50 | 42.47 | 42.19 | 42.26 | 44.71 | 48.23 | 46.68 | 46.08 | 45.19 | 43.77 |
| 9 | 45.17 | 46.39 | 47.65 | 48.75 | 49.34 | 49.52 | 49.35 | 49.47 | 52.35 | 56.55 | 54.78 | 54.07 | 53.00 | 51.29 |
| 10 | 49.52 | 51.40 | 53.16 | 54.75 | 55.78 | 56.37 | 56.56 | 56.78 | 60.12 | 64.98 | 63.06 | 62.25 | 61.05 | 59.05 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 73.717 | 63.063 |
| SC2 | 0 | 8 | 49.375 | 42.260 |
| SC3 | -18 | 7 | 41.363 | 35.733 |
| SC4 | -25 | 6 | 33.334 | 29.002 |
| SC5 | -34 | 6 | 33.015 | 29.033 |
| A | 3415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| G | 1035 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.