EA-250BC7-C10 C
18.02 kW
Defrost: None
Product code: EA-435AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,454 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 65.7 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 102 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-435AE6-C01 C | None |
|---|---|
| EA-435AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.91 | 6.97 | 7.05 | 7.12 | 7.14 | 7.11 | 7.04 | 7.24 | 7.72 | 8.38 | 8.22 | 8.17 | 8.09 | 7.95 |
| 5 | 8.92 | 9.14 | 9.35 | 9.53 | 9.61 | 9.60 | 9.53 | 9.71 | 10.32 | 11.19 | 10.89 | 10.79 | 10.65 | 10.46 |
| 6 | 10.88 | 11.29 | 11.67 | 11.99 | 12.17 | 12.20 | 12.15 | 12.32 | 13.08 | 14.17 | 13.75 | 13.59 | 13.35 | 12.97 |
| 7 | 12.61 | 13.22 | 13.78 | 14.28 | 14.60 | 14.79 | 14.80 | 15.00 | 15.91 | 17.25 | 16.74 | 16.54 | 16.23 | 15.71 |
| 8 | 14.13 | 14.96 | 15.73 | 16.31 | 16.77 | 17.04 | 17.15 | 17.41 | 18.49 | 20.09 | 19.59 | 19.38 | 19.04 | 18.48 |
| 9 | 15.52 | 16.50 | 17.48 | 18.35 | 18.95 | 19.33 | 19.51 | 19.81 | 21.04 | 22.84 | 22.30 | 22.05 | 21.66 | 20.96 |
| 10 | 16.79 | 18.01 | 19.23 | 20.32 | 21.09 | 21.59 | 21.85 | 22.22 | 23.60 | 25.62 | 25.04 | 24.75 | 24.31 | 23.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.036 |
| SC2 | 0 | 8 | 17.410 |
| SC3 | -18 | 7 | 14.426 |
| SC4 | -25 | 6 | 11.667 |
| SC5 | -34 | 6 | 10.984 |
| A | 2357 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2357 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.