EA-250AG6-C09 C
26.77 kW
Defrost: None
Product code: EA-440AG4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,239 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 155.9 m² |
| Inner volume | 32.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 169 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-440AG4-C01 C | None |
|---|---|
| EA-440AG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.31 | 11.29 | 11.33 | 11.42 | 11.43 | 11.38 | 11.27 | 11.64 | 12.43 | 13.53 | 13.27 | 13.20 | 13.11 | 12.99 |
| 5 | 14.48 | 14.56 | 14.71 | 14.86 | 14.90 | 14.84 | 14.68 | 14.96 | 15.91 | 17.27 | 16.77 | 16.60 | 16.35 | 15.97 |
| 6 | 17.56 | 17.82 | 18.11 | 18.39 | 18.49 | 18.43 | 18.24 | 18.45 | 19.56 | 21.19 | 20.47 | 20.19 | 19.78 | 19.10 |
| 7 | 20.61 | 21.07 | 21.53 | 21.92 | 22.12 | 22.11 | 21.88 | 22.06 | 23.34 | 25.23 | 24.34 | 23.96 | 23.40 | not rated |
| 8 | 23.41 | 24.15 | 24.85 | 25.47 | 25.79 | 25.83 | 25.59 | 25.75 | 27.22 | 29.37 | 28.34 | 27.88 | not rated | not rated |
| 9 | 25.97 | 26.98 | 27.94 | 28.78 | 29.29 | 29.46 | 29.34 | 29.45 | 31.12 | 33.54 | 32.39 | 31.84 | not rated | not rated |
| 10 | 28.33 | 29.67 | 30.91 | 31.87 | 32.55 | 32.83 | 32.78 | 33.01 | 34.93 | 37.68 | 36.49 | 35.87 | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.487 |
| SC2 | 0 | 8 | 25.745 |
| SC3 | -18 | 7 | 22.025 |
| SC4 | -25 | 6 | 18.109 |
| SC5 | -34 | 6 | 17.636 |
| A | 2567 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2567 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.